Belden 3088A Pair or 3089A Triad for 18 AWG Instrumentation

Use 3088A for one 18 AWG pair at 0.276 in and 600 V (TC). Use 3089A for one 18 AWG triad at 0.290 in and 600 V (TC-ER). Both list 5 A and 7.06 Ohm/1000ft.

Rust Belt Industrials · November 5, 2026 · 5 min read

On this page

Use Belden 3088A when the instrumentation cable is one 18 AWG pair. As of November 5, 2026, that sheet lists a black PVC jacket of 0.276 in (7.01 mm), 5 A per conductor at 25°C, and 600 V (TC) with 150 V (NPLF). Use Belden 3089A when the instrumentation cable is one 18 AWG triad. As of the same day, that sheet lists a black PVC jacket of 0.290 in (7.37 mm), the same 5 A at 25°C, and 600 V (TC-ER) with 150 V (NPLF). Both list 18 AWG 7x26 bare copper, conductor DCR of 7.06 Ohm/1000ft, and UL temperature 90°C dry and 90°C wet. Neither title says DeviceNet. The DeviceNet thick and thin cables are 3082A and 3084A, on the DeviceNet page.

The same 18 AWG conductor, as a pair or as a triad

As of November 5, 2026, 3088A's title is Inst, 1 Pr #18. The description is one pair, 18 AWG (7x26) bare copper, PVC-nylon insulation, E1 color code, overall Beldfoil shield, black PVC jacket, 600 V TC, 150 V NPLF, 90°C dry/wet, and the description includes SUN RES DIR BUR. Insulation is PVC/nylon, 0.022 in (0.56 mm) thick, nominal insulation diameter 0.088 in (2.2 mm), colors black and white. The shield is a 100% bi-laminate tape with a 20 AWG (7x28) tinned-copper drain. The jacket is PVC, 0.047 in (1.2 mm) thick, nominal diameter 0.276 in (7.01 mm), with a ripcord. 3089A's title is Inst, 1 Tri #18. Conductor, insulation thickness, insulation diameter, shield, drain, and jacket thickness match. Insulation colors are black, white, and red. Nominal jacket diameter is 0.290 in (7.37 mm). The description says 600 V TC-ER rather than 600 V TC, and the application line adds RTD where 3088A names encoders. Both application cells name industrial control, raceways, cable trays and ducts, digital control, instruments, low voltage digital control, control circuits, DCS, PLC, solenoids, valves, actuators, and positioners. Neither sheet prints the other part number.

3088A and 3089A rows from the technical data sheets opened November 5, 2026.
Item3088A3089A
Element1 pair, black and white1 triad, black, white, red
JacketPVC, 0.276 inPVC, 0.290 in
Conductor DCR7.06 Ohm/1000ft7.06 Ohm/1000ft
Current5 A at 25°C5 A at 25°C
Shield DCR8.49 Ohm/1000ft8.08 Ohm/1000ft
Voltage600 V (TC), 150 V (NPLF)600 V (TC-ER), 150 V (NPLF)
Bend radius2.8 in3.5 in
Pull tension57 lbs80 lbs

7.06 Ohm/1000ft and 5 A match, and the shield DCR does not

As of November 5, 2026, both conductor-DCR cells print 7.06 Ohm/1000ft, with no kilometer figure in that cell. 3088A lists capacitance conductor to conductor of 41.3 pF/ft (135 pF/m) and capacitance conductor to shield of 74.3 pF/ft (244 pF/m). Inductance is 0.1945 µH/ft (0.6381 µH/m). 3089A lists 47.3 pF/ft (155 pF/m) and 84.2 pF/ft (276 pF/m). Inductance is 0.199 µH/ft (0.653 µH/m). Current is 5 A per conductor at 25°C on both. Outer-shield DCR is 8.49 Ohm/1000ft (27.9 Ohm/km) on 3088A and 8.08 Ohm/1000ft (26.5 Ohm/km) on 3089A. 3088A's voltage cell is 600 V (TC) and 150 V (NPLF). 3089A's voltage cell is 600 V (TC-ER) and 150 V (NPLF). NEC / UL compliance is Article 336, Article 760, NPLF, TC on 3088A, and Article 336, Article 760, NPLF, TC-ER on 3089A.

TC on the pair, TC-ER on the triad

As of November 5, 2026, both sheets list UL temperature 90°C dry and 90°C wet. Operating temperature is -30°C to +90°C dry, and 75°C wet. Stationary and installation bend radius is 2.8 in (71 mm) on 3088A and 3.5 in (89 mm) on 3089A. Pull tension is 57 lbs (26 kg) on 3088A and 80 lbs (36 kg) on 3089A. Bulk weight is 37 lbs/1000ft on 3088A and 47 lbs/1000ft on 3089A. Suitability on both is indoor, outdoor, sunlight resistance, and burial. Flammability on 3088A is UL 1685 UL Loading, T-29-520, IEEE 1202, and FT4. Flammability on 3089A is UL 1685 UL Loading, IEEE 1202, and FT4, and does not print T-29-520. Page revision is 0.602 on 3088A and 0.600 on 3089A, both dated 04-10-2026. The 3088A variant row is 3088A 01010000, black reel, 10,000 ft. 3089A lists 3089A 0105000, black reel, 5,000 ft, and 3089A 01010000, black reel, 10,000 ft.

What to copy onto the cable line

  • Part: 3088A or 3089A, from the sheet opened November 5, 2026.
  • Element: 1 pair, black and white, or 1 triad, black, white, and red.
  • Conductor: 18 AWG 7x26 bare copper. Insulation: PVC/nylon, 0.088 in.
  • Jacket: black PVC at 0.276 in, or black PVC at 0.290 in.
  • DCR: 7.06 Ohm/1000ft. Current: 5 A per conductor at 25°C.
  • Shield DCR: 8.49 Ohm/1000ft, or 8.08 Ohm/1000ft.
  • Voltage: 600 V (TC) and 150 V (NPLF), or 600 V (TC-ER) and 150 V (NPLF).
  • Temperature: UL 90°C dry and 90°C wet. Operating: -30°C to +90°C dry, 75°C wet.

3088A or 3089A note

Name the pair or the triad. The voltage cell is TC on 3088A and TC-ER on 3089A.

This prepares a request. It does not send one.

Questions these sheets answer

Is 3088A a DeviceNet cable?

3088A's title and description say instrumentation, 600 V TC, and 150 V NPLF, as of November 5, 2026. They do not say DeviceNet. 3089A's title says one triad and TC-ER. DeviceNet thick and thin on this site are 3082A and 3084A.

Does the triad keep the TC voltage cell?

3088A prints 600 V (TC) and 150 V (NPLF), as of November 5, 2026. 3089A prints 600 V (TC-ER) and 150 V (NPLF). The NEC line changes from TC to TC-ER with that cell. Conductor DCR and the 5 A cell stay the same.

Which colors are the triad?

3088A's color code is black and white, as of November 5, 2026. 3089A's color code is black, white, and red. Jacket color on both variant tables is black.

Sources

Element, diameter, voltage, current, and DCR are from the Belden 3088A and 3089A technical data sheets. Both were opened November 5, 2026. Neither sheet names the other part number. Both titles are instrumentation cable at 18 AWG 7x26.