Skip to the guide

Industrial networking

Belden 3105A PLTC or 9841 CM

Use 3105A for one 22 AWG pair at 6 A, PLTC, and an outdoor line. Use 9841 for one 24 AWG pair at 2.1 A, CM, and indoor.

Rust Belt Industrials · October 26, 2026 · 5 min read

On this page

Use Belden 3105A when the one-pair RS-485 cable is the harsh-applications row: 22 AWG, CM and PLTC, with outdoor, sunlight, and oil on the suitability line. As of October 26, 2026, that sheet lists one 22 AWG (7x30) tinned-copper pair, a nominal jacket diameter of 0.294 in (7.47 mm), 120 Ohm, and 6 A per conductor at 30°C. Use Belden 9841 when the one-pair cable is the light-industrial row: 24 AWG and CM, with indoor on the suitability line. As of the same day, that sheet lists one 24 AWG (7x32) tinned-copper pair, a nominal jacket diameter of 0.232 in (5.89 mm), 120 Ohm, and 2.1 A per conductor at 25°C with a 10°C temperature rise in the current cell. The category page places 3105A in the industrial and harsh table and 9841 in the light-industrial table. A second pair at 24 AWG is 9842, on the 9841 and 9842 page.

Two category tables, one pair on each sheet

As of October 26, 2026, the harsh-applications table lists 3105A at SF/UTP, 1 pair, and 22 AWG. On that row the jacket and rating cells do not place the part number in the technical-data column, so the listing is copied from the sheet: 300 V (CM, PLTC). The light-industrial table lists 9841 at SF/UTP, 1 pair, 24 AWG, and PVC, and prints CMG in the rating cell. The 9841 sheet prints CM. Copy the sheet. The 150 Ohm comparison stays on the 9841 and 3079A page.

22 AWG foam polyethylene, or 24 AWG polyethylene

As of October 26, 2026, 3105A insulation is foam polyethylene, 0.029 in (0.74 mm), nominal insulation diameter 0.087 in (2.2 mm), colors white/blue stripe and blue/white stripe, notes HDPE. The description line says Datalene. The shield is a 100% bi-laminate tape with a 22 AWG (7x30) tinned-copper drain, plus a 65% tinned-copper braid. The jacket is PVC, 0.047 in (1.2 mm), nominal diameter 0.294 in (7.47 mm), tolerance +/- 0.006 in. 9841 insulation is polyethylene, 0.023 in (0.58 mm), nominal insulation diameter 0.068 in (1.7 mm), the same stripe colors. Its shield is a 100% bi-laminate tape with a 24 AWG (7x32) tinned-copper drain, plus a 90% tinned-copper braid. Its jacket is PVC, 0.035 in (0.89 mm), nominal diameter 0.232 in (5.89 mm), tolerance +/- 0.020 in.

One-pair rows from the sheets opened October 26, 2026.
Item3105A9841
Category blockIndustrial and harsh, 1 pair, 22 AWGLight industrial, 1 pair, 24 AWG
Conductor22 AWG, 7x30, tinned copper24 AWG, 7x32, tinned copper
Nominal jacket OD0.294 in (7.47 mm)0.232 in (5.89 mm)
BraidTinned copper, 65%Tinned copper, 90%
Impedance120 Ohm120 Ohm
Current cell6 A per conductor at 30°C2.1 A per conductor at 25°C, 10°C rise
Operating range-20°C to +60°C-30°C to +80°C
UL voltage300 V (CM, PLTC)300 V (CM), 30 V (UL AWM 2919)

120 Ohm, with different DCR, capacitance, and velocity

As of October 26, 2026, 3105A lists conductor DCR of 18.2 Ohm/1000ft, with no kilometer figure in that cell, capacitance of 11 pF/ft (36 pF/m) conductor to conductor and 20.9 pF/ft (68.6 pF/m) conductor to other, impedance of 120 Ohm, velocity of 78%, and insertion loss of 0.5 dB/100ft at 1 MHz. Outer-shield DCR is 4.685 Ohm/1000ft (15.37 Ohm/km). The sheet does not print inductance. 9841 lists conductor DCR of 24 Ohm/1000ft (79 Ohm/km), capacitance of 12.8 pF/ft (42.0 pF/m) and 23 pF/ft (75 pF/m), delay of 1.6 ns/ft, velocity of 66%, and insertion loss of 0.6 dB/100ft at 1 MHz. Outer-shield DCR is 3.4 Ohm/1000ft (11 Ohm/km). The 30 V AWM 2919 line is on 9841. 3105A's voltage cell does not print an AWM style.

PLTC and oil on 3105A, indoor CM on 9841

As of October 26, 2026, 3105A lists UL temperature 60°C and operating temperature -20°C to +60°C. Minimum bend radius is 3.372 in (85.65 mm), stationary and installation. Maximum pull tension is 53.34 lbs (24.19 kg). Bulk weight is 43 lbs/1000ft, with no kilogram in that cell. Suitability is indoor, outdoor, sunlight resistance, and oil resistance. Flammability is UL 1685 UL Loading and IEC 60332-1-2. NEC compliance is Article 725, Article 800, CM, PLTC. CEC compliance is CM. The notes say oil resistance passes Oil Res II per UL 1277, Table 10.17, and that a CPE jacket is ordered as YR44345. That CPE page was not opened. Page revision is 0.598, dated 02-20-2026.

As of October 26, 2026, 9841 lists UL temperature 80°C and operating temperature -30°C to +80°C. Minimum bend radius is 2.5 in (64 mm). Maximum pull tension is 72.3 lbs (32.8 kg). Weight is 36 lbs/1000ft (54 kg/km). Suitability is indoor. NEC compliance is Article 800, CM. AWM compliance is AWM 2919. The other-standard cell says DMX-512. 3105A's standards block does not print DMX-512. A single extra conductor beside a 22 AWG pair is 3106A, on the 3105A and 3106A page.

What to copy onto the cable line

  • Part: 3105A or 9841, from the sheet opened October 26, 2026.
  • Gauge: 22 AWG 7x30, or 24 AWG 7x32.
  • Nominal diameter: 0.294 in (7.47 mm), or 0.232 in (5.89 mm).
  • Current: 6 A per conductor at 30°C, or 2.1 A per conductor at 25°C with the 10°C rise note.
  • Listing: 300 V (CM, PLTC), or 300 V (CM) and 30 V (UL AWM 2919).
  • Place: indoor, outdoor, sunlight, and oil, or indoor.

3105A or 9841 note

Name the gauge and the listing from the sheet you are copying.

This prepares a request. It does not send one.

Questions these sheets answer

Does one pair mean the gauges match?

Both sheets list one pair and 120 Ohm, as of October 26, 2026. 3105A is 22 AWG. 9841 is 24 AWG. The category puts them in different application tables. Pair count does not choose the gauge.

Which current cell has a rise note?

3105A prints 6 A per conductor at 30°C and does not print a rise note, as of October 26, 2026. 9841 prints 2.1 A per conductor at 25°C and a 10°C temperature rise. The temperatures in the cells are 30°C and 25°C.

Can PLTC be copied onto 9841?

PLTC is on the 3105A voltage cell, as of October 26, 2026. The harsh-table row for 3105A does not place the part number in the technical-data column, so the request uses the sheet. The 9841 sheet prints CM. The 9841 row in the light-industrial table prints CMG.

Sources

Gauge, diameter, current, voltage, temperature, and suitability are from the Belden 3105A and 9841 technical data sheets. The harsh and light-industrial rows are from the Belden RS-485 category page. All three were opened October 26, 2026. YR44345 was named and not opened.