Power connections
Laminated Busbar Insulation Film
Match the film to the continuous-use temperature and the dielectric cell on Storm's table. Kapton is the 400°C row. Mylar and Tedlar are the 105°C rows.
On this page
Use Mylar or Tedlar when the continuous-use cell is 105°C. Use epoxy powder when that cell is 130°C. Use FR4 or Teonex when it is 140°C. Use Nomex when it is 220°C. Use Kapton when it is 400°C. As of November 7, 2026, Storm's insulating-films table lists Mylar at dielectric constant 3.3 and 7500 in the volts-per-ml column, Tedlar at 11.0 and 3500, epoxy powder at 4.0 and 800, FR4 at 4.3 and 1250, Teonex at 3.4 and 5000, Nomex at 1.6 and 430 to 845, and Kapton at 3.7 and 5000. The column header on that table reads Volts per ml. A laminated busbar series rated 105°C, 130°C, or 180°C as a finished part is the MHi-T page, which is a working temperature for the busbar, not this film table.
Storm's table assigns a continuous-use temperature to each film
The films page opened November 7, 2026 says laminated conductors can be positioned as close as 0.005 inch apart, separated by a thin insulator. It says each dielectric coating has characteristics for a specific application, and that insulation thickness, type, and construction follow the application's temperature, ampacity, environment, and installation. The table columns are material, continuous use temperature in °C, dielectric constant under ASTM D150, dielectric strength under ASTM D149 with the header Volts per ml, flammability, and a characteristics line. Mylar is also labeled PET. Tedlar is also labeled PVF. Teonex is also labeled PEN. FR4 is labeled epoxy glass.
As of November 7, 2026, Mylar's characteristics line says cost effective, tear resistant, chemical resistant, and moisture resistant, at UL 94 VTM-0. Tedlar's line says chemical and solvent resistant, with good mechanical properties, at UL 94 HB. Epoxy powder's line says flame and moisture resistant, and ideal for multiple shapes, at UL 94 V-0. FR4's line says superior mechanical and dimensional stability, at UL 94 V-0. Teonex's line says higher deflective strength and continuous use temperature, at UL 94 VTM-0. Nomex's line says flame resistant and durable, at UL 94 V-0. Kapton's line says high temperature rating and range stability, at UL 94 VTM-0. Nomex is the row whose dielectric strength is a range, 430 to 845, rather than one figure.
| Film | Continuous use | Dielectric constant | Dielectric strength cell | Flammability |
|---|---|---|---|---|
| Mylar (PET) | 105°C | 3.3 | 7500 | UL 94 VTM-0 |
| Tedlar (PVF) | 105°C | 11.0 | 3500 | UL 94 HB |
| Epoxy powder | 130°C | 4.0 | 800 | UL 94 V-0 |
| FR4 epoxy glass | 140°C | 4.3 | 1250 | UL 94 V-0 |
| Teonex (PEN) | 140°C | 3.4 | 5000 | UL 94 VTM-0 |
| Nomex | 220°C | 1.6 | 430 to 845 | UL 94 V-0 |
| Kapton | 400°C | 3.7 | 5000 | UL 94 VTM-0 |
Two films can share a temperature and still differ on the dielectric cell
Mylar and Tedlar are both 105°C, as of November 7, 2026. Mylar's dielectric constant is 3.3 and its strength cell is 7500, at UL 94 VTM-0. Tedlar's dielectric constant is 11.0 and its strength cell is 3500, at UL 94 HB. A 105°C film request still has to name which of those two rows, because the flammability rating and the dielectric cells are different. FR4 and Teonex are both 140°C. FR4 is 4.3 and 1250, at UL 94 V-0, with the mechanical-stability line. Teonex is 3.4 and 5000, at UL 94 VTM-0, with the higher-deflective-strength line. Kapton is the only 400°C row. Nomex is the only 220°C row. Epoxy powder is the only 130°C row on this table.
Storm's dielectric-finishing page, opened November 7, 2026, states the epoxy figure as 800 volts per mil at a minimum of 10 mils, which is 0.010 inch. The films table's epoxy cell is 800 under a header that reads Volts per ml. The same dielectric page says powder thickness ranges from 6 to 120 mils, or 0.006 to 0.120 inch, that tensile strength on raw and plated copper bar is in the range of 7500 psi, and that the UL rating is 130°C. The 130°C figure agrees with the films table. The dielectric page also says a hipot test is recommended rather than relying on film thickness alone, and that edge conditioning for the powder can include hand sanding, tumbling, and a machined radius if required. It does not print the radius.
Mersen's design guide names series for roles, without this volts column
Mersen's laminated bus bar design guide, opened November 7, 2026, lists Nomex, Tedlar, Mylar, Kapton, epoxy-glass, and epoxy powder among the dielectrics it uses. Its Amron series notes assign roles. Amron 3 is polyimide film, recommended for high temperature applications, trade name Kapton, and the standards table lists MIL-P-46112. Amron 2 is aromatic polyamide paper, trade name Nomex, MIL-I-24204, described for mechanical toughness, thermal stability, and solvent resistance. Amron 6 is polyethylene terephthalate film, trade name Mylar, MIL-I-631. Amron 1 is polyvinyl fluoride, trade name Tedlar, L-P-1040. Amron 4, Mylar/Tedlar, is outside insulation and a scuff-resistant coating. Amron 5, Tedlar/Mylar/Tedlar, is internal insulation for high dielectric strength. Amron 7, Nomex/Mylar/Nomex, combines Nomex toughness with Mylar's electrical properties. Amron 9 is epoxy powder, ASTM D3451, for geometry where a film is not practical. Amron 8 is FR-4, MIL-I-24768/27.
The design guide does not print Storm's volts-per-ml column, and Storm's table does not print Amron series numbers. As of November 7, 2026, copy the continuous-use temperature and the dielectric cells from Storm's table. Copy the Amron number and the MIL or ASTM standard from Mersen when the drawing names that series. Kapton's 400°C cell is the film's continuous-use temperature on Storm's table. It is not the working temperature of a finished MHi-T busbar. The guide also says most insulating systems are UL Recognized under file E53800, and that values may fluctuate after the insulation has been applied. Teonex appears on Storm's table and does not appear in the Amron standards list that was read.
What to copy onto the film line
- Film: Mylar, Tedlar, epoxy powder, FR4, Teonex, Nomex, or Kapton, from Storm's table opened November 7, 2026.
- Continuous-use temperature from that row: 105°C, 130°C, 140°C, 220°C, or 400°C.
- Dielectric constant and the dielectric-strength cell. The header reads Volts per ml.
- Flammability: UL 94 VTM-0, UL 94 V-0, or UL 94 HB, from that row.
- Amron series and the MIL or ASTM standard, when the drawing uses Mersen's names.
- Epoxy thickness, when the coat is powder: 6 to 120 mils on the dielectric-finishing page, and 800 volts per mil at a minimum of 10 mils.
Questions these film pages answer
Which 105°C film is UL 94 VTM-0?
Mylar is 105°C, dielectric constant 3.3, strength cell 7500, and UL 94 VTM-0, as of November 7, 2026. Tedlar is 105°C, dielectric constant 11.0, strength cell 3500, and UL 94 HB.
Does Kapton's 400°C cell set the busbar working temperature?
Storm's table lists Kapton at 400°C continuous use, as of November 7, 2026. That cell is the film row. Mersen's MHi-T working temperatures are on the MHi-T page. The two figures are not substitutes.
What unit does the strength column name?
The films table header reads Volts per ml, as of November 7, 2026. The dielectric-finishing page states the epoxy 800 figure as 800 volts per mil at a minimum of 10 mils. The epoxy cell on the films table is 800.
Sources
Continuous-use temperature, dielectric constant, the volts-per-ml column, and flammability are from Storm's insulating-films table. Epoxy thickness, 800 volts per mil, 7500 psi, and the 130°C UL line are from Storm's dielectric-finishing page. Amron series names and standards are from Mersen's laminated bus bar design guide. All three were opened November 7, 2026.