Industrial networking
Belden 1334A One Pair or 1327A Two Pair
Use 1334A for one 18 AWG pair at 0.287 in with a 65% braid. Use 1327A for two 18 AWG pairs at 0.44 in with foil on each pair and an overall foil. Both list 5.2 A and 100 Ohm.
On this page
Use Belden 1334A when the Type A industrial cable is one 18 AWG pair. As of November 6, 2026, that sheet lists a PVC jacket of 0.287 in (7.29 mm), a 65% tinned-copper braid, 5.2 A per conductor with no temperature in the cell, and 100 Ohm. Use Belden 1327A when the industrial cable is two 18 AWG pairs. As of the same day, that sheet lists a PVC jacket of 0.44 in (11 mm), individual and overall foil with no braid line, the same 5.2 A with no temperature in the cell, and the same 100 Ohm. The category places both under 300 V Type A PLTC/ITC-ER, 18 AWG, standard industrial-grade: 1334A at one pair, and 1327A at two pair. The extra-rugged TPE row at one pair is on the 1334A and 2100A page.
One pair with a braid, or two pairs with foil on each pair
As of November 6, 2026, both descriptions say PO insulation and an orange PVC jacket, CMG. Both insulation cells say polypropylene. 1334A's colors are blue and orange. 1327A's colors are blue, orange, and numbered. 1334A's shield is a 100% bi-laminate tape and a 65% tinned-copper braid. 1327A's shield is an inner 100% bi-laminate tape and an outer 100% bi-laminate tape. The 1327A shield block does not print a braid. 1334A's jacket is PVC, 0.065 in (1.7 mm), 0.287 in (7.29 mm), with a ripcord. 1327A's jacket is PVC, 0.053 in (1.3 mm), 0.44 in (11 mm). The jacket line that was read does not print a ripcord word. Neither sheet names the other part number. Neither insulation cell prints a thickness.
| Item | 1334A | 1327A |
|---|---|---|
| Pairs | 1, 18 AWG | 2, 18 AWG |
| Shield | Foil plus 65% braid | Foil on each pair, and overall foil |
| Jacket | PVC, 0.287 in | PVC, 0.44 in |
| Current | 5.2 A, no temperature | 5.2 A, no temperature |
| Conductor DCR | 7.2 Ohm/1000ft | 7.2 Ohm/1000ft |
| Outer shield DCR | 3.8 Ohm/1000ft | 4.9 Ohm/1000ft |
| UL temperature | 90°C | 105°C |
| Pull tension | 44.8 lbs | 89.6 lbs |
100 Ohm and 5.2 A, and the shield DCR follows the pair count
As of November 6, 2026, both conductor-DCR cells print 7.2 Ohm/1000ft with no kilometer figure. Both list capacitance of 45 pF/ft (150 pF/m), unbalance of 1.2 pF/ft, impedance of 100 Ohm, and velocity of 66%. 1327A also lists inductance of 0.19 µH/ft (0.62 µH/m) and inner-shield DCR of 1.51 Ohm/1000ft (4.95 Ohm/km). 1334A's electrical block that was read does not print inductance or an inner-shield DCR. Outer-shield DCR is 3.8 Ohm/1000ft (12 Ohm/km) on 1334A and 4.9 Ohm/1000ft (16 Ohm/km) on 1327A. Insertion loss is 0.069 dB/100ft on 1334A and 0.08 dB/100ft on 1327A, and neither line prints a frequency. Voltage is 300 V RMS on both. NEC / UL compliance is Article 725, Article 727, Article 800, CMG, ITC, PLTC on both. CEC compliance is CMG on both.
UL 90°C on one pair, UL 105°C on two pair
As of November 6, 2026, 1334A lists UL temperature 90°C and operating temperature -40°C to +105°C. Bend radius is 3.37 in (85.6 mm), stationary and installation. Pull tension is 44.8 lbs (20.3 kg). Bulk weight is 60 lbs/1000ft. Suitability does not print burial. 1327A lists UL temperature 105°C and operating temperature -40°C to +105°C. Bend radius is 4.46 in (113 mm), stationary and installation. Pull tension is 89.6 lbs (40.6 kg). Bulk weight is 90 lbs/1000ft. Suitability lists indoor, outdoor, sunlight resistance, UV resistance, oil resistance twice, and burial. Flammability on both includes UL1685 FT4 Loading, 1202, and IEC 60332-3-24. CPR is Euroclass Eca on both. The standards blocks that were read do not print ISA/SP-50 Type A. The category page is the page that calls both standard industrial-grade Type A.
3,280 ft is a 1334A length
As of November 6, 2026, 1334A lists light blue at 1,000 ft and at 3,280 ft, and orange at 1,000 ft and at 3,280 ft, footnote C. 1327A lists 1327A 0061000 light blue at 1,000 ft and 1327A 0031000 orange at 1,000 ft, footnote C. It does not print a 3,280 ft row. Page revision is 0.569 on 1334A and 0.572 on 1327A, both dated 02-20-2026. The flexible one-pair foil cable at 0.280 in is on the 3076F and 1334A page.
What to copy onto the cable line
- Part: 1334A or 1327A, from the sheet opened November 6, 2026.
- Pairs: 1, or 2. Both are 18 AWG 7x26 tinned copper.
- Shield: foil plus a 65% braid, or foil on each pair and an overall foil.
- Jacket: PVC at 0.287 in, or PVC at 0.44 in.
- Impedance: 100 Ohm. Current: 5.2 A, with no temperature in either cell.
- Conductor DCR: 7.2 Ohm/1000ft. Outer-shield DCR: 3.8 Ohm/1000ft, or 4.9 Ohm/1000ft.
- Voltage: 300 V RMS. NEC includes CMG, ITC, and PLTC on both.
- UL temperature: 90°C, or 105°C. Operating range is -40°C to +105°C on both.
Questions these pages answer
Does the two-pair sheet keep the 65% braid?
1334A prints a 65% tinned-copper braid, as of November 6, 2026. 1327A's shield block prints two foil tapes and does not print a braid. Pair count and that shield stack are the split.
Does two pair keep UL 90°C?
1334A's UL temperature is 90°C, as of November 6, 2026. 1327A's UL temperature is 105°C. Both operating ranges print -40°C to +105°C.
Which suitability cell says burial?
1327A's suitability cell includes burial, as of November 6, 2026. 1334A's suitability cell does not. Both descriptions still say an orange PVC jacket and CMG.
Sources
Pair count, shield, diameter, current, and temperature are from the Belden 1334A and 1327A technical data sheets. The one-pair and two-pair Type A labels are from the Belden Foundation Fieldbus category. All three were opened November 6, 2026. Neither sheet names the other part number.