Skip to the guide

Industrial networking

Belden 3106A PVC or 3106DB CPE Direct Burial

Use 3106A for the PVC jacket at 0.310 in, UL 60°C, and Oil Res II. Use 3106DB for the CPE jacket at 0.359 in, a waterblock tape, UL 90°C, and a Dir Bur title. Both list 120 Ohm and 6 A at 30°C.

Rust Belt Industrials · November 6, 2026 · 6 min read

On this page

Use Belden 3106A when the 1.5-pair 22 AWG RS-485 cable is the PVC jacket. As of November 6, 2026, that sheet lists a jacket of 0.310 in (7.87 mm), 6 A per conductor at 30°C, UL temperature 60°C, operating temperature -20°C to +60°C, and 120 Ohm. Use Belden 3106DB when the jacket is CPE and the title says Dir Bur. As of the same day, that sheet lists a jacket of 0.359 in (9.12 mm), a waterblock tape, the same 6 A at 30°C, the same 120 Ohm, UL temperature 90°C, and operating temperature -40°C to +90°C. The RS-485 category lists 3106A on the 1.5 pair, 22 AWG, SF/UTP row of the industrial table, and 3106DB on the 1.5 pair, 22 AWG, SF/UTP row of the following block. The one-pair choice is on the 3105A and 3106A page.

The same pair plus one conductor, and a different jacket

As of November 6, 2026, both sheets list one pair of 22 AWG 7x30 tinned copper and one extra conductor of 22 AWG 7x30 tinned copper. Pair insulation is foam polyethylene, 0.033 in (0.84 mm), nominal insulation diameter 0.095 in (2.4 mm), colors white/orange stripe and orange/white stripe, with an HDPE note. The extra conductor is PVC insulation, 0.017 in (0.43 mm), nominal insulation diameter 0.062 in (1.6 mm), color blue/white stripe. The shield on both is a 100% bi-laminate tape, a 22 AWG (7x30) tinned-copper drain, and a 65% tinned-copper braid. 3106A's jacket is PVC, 0.047 in (1.2 mm), 0.310 in (7.87 mm). 3106DB's jacket is CPE, 0.055 in (1.4 mm), 0.359 in (9.12 mm). 3106DB prints a waterblock tape under the shield. 3106A's shield block does not. 3106A's description says PVC jacket, CM, PLTC, sunlight resistant, and oil resistant. 3106DB's description adds DIR BUR.

3106A and 3106DB rows from the technical data sheets opened November 6, 2026.
Item3106A3106DB
JacketPVC, 0.310 inCPE, 0.359 in
WaterblockNo waterblock lineWaterblock tape
Impedance120 Ohm120 Ohm
Current6 A at 30°C6 A at 30°C
UL temperature60°C90°C
Operating range-20°C to +60°C-40°C to +90°C
Oil noteOil Res IIOil Res I and Oil Res II
Title burial wordNo Dir Bur in the titleDir Bur

120 Ohm, 18.2 Ohm/1000ft, and 6 A at 30°C on both

As of November 6, 2026, both pair cells list conductor DCR of 18.2 Ohm/1000ft, capacitance conductor to conductor of 11 pF/ft (36 pF/m), capacitance conductor to other of 20.9 pF/ft (68.6 pF/m), impedance of 120 Ohm, inductance of 0.203 µH/ft (0.666 µH/m), velocity of 78%, and 6 A per conductor at 30°C. The extra-conductor cell on each sheet lists 18.2 Ohm/1000ft (59.7 Ohm/km) and 6 A per conductor at 30°C. The pair DCR cell does not print the kilometer figure. Outer-shield DCR is 4.544 Ohm/1000ft (14.91 Ohm/km) on both. Insertion loss at 1 MHz is 0.5 dB/100ft on both. Voltage is 300 V (CM, PLTC) on both. NEC / UL compliance is Article 725, Article 800, CM, PLTC on both. CEC compliance is CM on both.

UL 60°C on PVC, UL 90°C on CPE, and YR46721 is a different number

As of November 6, 2026, 3106A lists UL temperature 60°C and operating temperature -20°C to +60°C. The temperature block does not print an installation cell. Bend radius is 3.6 in (91 mm), stationary and installation. Pull tension is 75.26 lbs (34.14 kg). Bulk weight is 48 lbs/1000ft. The oil note says Oil Res II per UL 1277, Table 10.17. The same note says a CPE jacketed version is ordered as YR46721. That page was not opened. 3106DB is the sheet whose title says Dir Bur and whose construction prints a waterblock tape. It is not given the YR46721 string. 3106DB lists UL temperature 90°C, operating temperature -40°C to +90°C, and installation temperature -20°C to +90°C. Bend radius is 4.308 in (109.4 mm). Pull tension is the same 75.26 lbs (34.14 kg). Bulk weight is 62 lbs/1000ft. The oil note says Oil Res I and Oil Res II per UL 1277, Table 10.17. 3106A's suitability is indoor, outdoor, sunlight resistance, and oil resistance. 3106DB's suitability cell uses those same words and does not add the word burial. The Dir Bur wording is in the title and the description. 3106A's application cell names harsh environment, IIoT, factory or process automation, video, audio, and data. 3106DB's application cell names direct burial, RS-485, PLCs, VFDs, HMIs, motors, RTU, SCADA, and outdoor solar and lighting.

Where the category table places the two numbers

As of November 6, 2026, the RS-485 category's industrial table lists 3106A at 1.5 pair, 22 AWG, SF/UTP. The jacket and rating cells on that continuation row were empty in the table that was read. The sheet is the page that says PVC, CM, and PLTC. The next block's first filled row is 3105DB, CPE, CM/PLTC, UL Direct Burial. 3106DB sits on the 1.5 pair row of that block. The jacket and rating cells on the 3106DB continuation row were also empty in the table that was read. The 3106DB sheet is the page that says CPE and Dir Bur. 3106A prints CPR Euroclass Eca and UKCA Class Eca. The 3106DB standards block that was read does not print those two lines. Page revision is 0.595, dated 02-20-2026, on 3106A, and 0.398, dated 10-07-2026, on 3106DB. The 3106DB text that was read does not print a put-up length. The three-pair and four-pair PVC and CPE pairs are on the 3108A and 3108DB page and the 3109A and 3109DB page.

What to copy onto the cable line

  • Part: 3106A or 3106DB, from the sheet opened November 6, 2026.
  • Elements: 1 pair plus 1 conductor, both 22 AWG 7x30 tinned copper.
  • Pair colors: white/orange stripe and orange/white stripe. Extra conductor: blue/white stripe.
  • Shield: foil, 22 AWG drain, 65% braid. 3106DB also has a waterblock tape.
  • Jacket: PVC at 0.310 in, or CPE at 0.359 in.
  • Impedance: 120 Ohm. Current: 6 A per conductor at 30°C, on the pair and on the extra conductor.
  • Voltage: 300 V (CM, PLTC).
  • Temperature: UL 60°C and -20°C to +60°C, or UL 90°C, operating -40°C to +90°C, installation -20°C to +90°C.
  • CPE note on 3106A: YR46721. That sheet was not opened. It is not the 3106DB number.

3106A or 3106DB note

Name the jacket. PVC is 3106A. CPE with a waterblock tape is 3106DB. YR46721 is a different number.

This prepares a request. It does not send one.

Questions these pages answer

Is 3106DB the YR46721 in the 3106A note?

3106A's note names YR46721 for a CPE jacket, as of November 6, 2026. That page was not opened. 3106DB is a different catalog number, with Dir Bur in the title and a waterblock tape on the sheet.

Does CPE keep 0.310 in?

3106A is 0.310 in (7.87 mm), as of November 6, 2026. 3106DB is 0.359 in (9.12 mm). Impedance, the 6 A cell, and the shield DCR stay the same.

Does the suitability cell say burial?

3106DB's suitability cell lists indoor, outdoor, sunlight resistance, and oil resistance, as of November 6, 2026. It does not add the word burial. The title and the description are the lines that say Dir Bur. The application cell says direct burial.

Sources

Jacket, waterblock, current, temperature, and the YR46721 note are from the Belden 3106A and 3106DB technical data sheets. The 1.5 pair row positions are from the Belden RS-485 category. All three were opened November 6, 2026. YR46721 was named and not opened.