Belden 82842 PVC or 89842 FEP for Two-Pair CMP

Use 82842 for the PVC CMP jacket at 0.273 in, 3.2 A, and UL 75°C. Use 89842 for the FEP CMP jacket at 0.345 in, 4 A, and UL 200°C. Both list 120 Ohm.

Rust Belt Industrials · November 5, 2026 · 5 min read

On this page

Use Belden 82842 when the two-pair CMP cable is the PVC jacket. As of November 5, 2026, that sheet lists a PVC jacket of 0.273 in (6.93 mm), 3.2 A per conductor at 25°C, UL temperature 75°C, and an operating range of 0°C to +75°C. Use Belden 89842 when the two-pair CMP cable is the FEP jacket. As of the same day, that sheet lists an FEP jacket of 0.345 in (8.76 mm), 4 A per conductor at 25°C, UL temperature 200°C, and an operating range of -70°C to +200°C. Both list two 24 AWG pairs, 120 Ohm, and 300 V (CMP). 9842's plenum-number cell, opened the same day, names 82842 and 89842. The one-pair CMP jackets, where 0.204 in and 4 A match, are on the 82841 and 89841 page.

Two pairs, and the insulation thickness changes with the jacket

As of November 5, 2026, both sheets list two pairs of 24 AWG 7x32 tinned copper. Pair colors are white/blue stripe and blue/white stripe, plus white/orange stripe and orange/white stripe. The shield is a 100% bi-laminate tape with a 24 AWG (7x32) tinned-copper drain, plus a 90% tinned-copper braid. 82842 insulation is FEP foam, 0.019 in (0.48 mm) thick, nominal insulation diameter 0.062 in (1.6 mm). The jacket is PVC, 0.015 in (0.38 mm) thick, nominal diameter 0.273 in (6.93 mm). 89842 insulation is FEP foam, 0.023 in (0.58 mm) thick, nominal insulation diameter 0.070 in (1.8 mm). The jacket is FEP, 0.020 in (0.51 mm) thick, nominal diameter 0.345 in (8.76 mm). Neither sheet prints a jacket OD tolerance. Suitable applications on both name RS-485 and the same serial-communication list as the one-pair CMP sheets. Neither plenum sheet prints the other part number.

82842 and 89842 rows from the technical data sheets opened November 5, 2026.
Item8284289842
JacketPVC, 0.273 inFEP, 0.345 in
Insulation diameter0.062 in0.070 in
Impedance120 Ohm120 Ohm
Current3.2 A at 25°C4 A at 25°C
Shield DCR2.4 Ohm/1000ft3.1 Ohm/1000ft
UL temperature75°C200°C
Operating range0°C to +75°C-70°C to +200°C
Cross-referenceNon-plenum number 9842Non-plenum number 9842

120 Ohm matches, and 3.2 A does not

As of November 5, 2026, both sheets list conductor DCR of 24 Ohm/1000ft, with no kilometer figure in that cell. Capacitance conductor to conductor is 12 pF/ft (39 pF/m). Capacitance to the other conductors plus shield is 22 pF/ft (72 pF/m). Impedance is 120 Ohm. Velocity is 76%. Neither electrical block prints a delay. Outer-shield DCR is 2.4 Ohm/1000ft (7.9 Ohm/km) on 82842 and 3.1 Ohm/1000ft (10 Ohm/km) on 89842. Current is 3.2 A per conductor at 25°C on 82842 and 4 A per conductor at 25°C on 89842. Nominal insertion loss at 1 MHz is 0.6 dB/100ft on both. The high-frequency table does not print a row past 1 MHz. Voltage is 300 V (CMP). NEC / UL compliance is Article 800, CMP. CEC / C(UL) compliance is CMP.

The two-pair FEP sheet is the larger cable

As of November 5, 2026, 82842's suitability cell is indoor. UL temperature is 75°C. Operating temperature is 0°C to +75°C. Bend radius is 2.75 in (69.9 mm) for stationary and installation use. Pull tension is 56.7 lbs (25.7 kg). Bulk weight is 38 lbs/1000ft. Flammability is NFPA 262, UL 910 (Plenum), FT6, and IEC 60332-1-2. CPR is Euroclass Eca. 89842's suitability cell is indoor and oil resistance. The notes cell says oil and gas resistant. UL temperature is 200°C. Operating temperature is -70°C to +200°C. Bend radius is 3.25 in (82.6 mm). Pull tension is 68 lbs (31 kg). Bulk weight is 44 lbs/1000ft. Flammability matches 82842. The European-directive cell includes REACH. Page revision is 0.544, dated 02-20-2026, on 82842, and 0.540, dated 02-20-2026, on 89842. Both non-plenum-number cells print 9842. 9842's own non-plenum cell still prints 9841ZH. That 9841ZH sheet was not opened.

Natural on 82842, red on 89842

As of November 5, 2026, 82842's variant rows are natural: 82842 8771000, 82842 877500, and 82842 8775000. Footnote C is on 8771000 and 877500. The table does not print a length. 89842's variant rows are red: 89842 0021000 and 89842 002500, both footnote C. That table does not print a length. The non-plenum two-pair cable at 0.340 in and 2.1 A is on the 9842 and 82842 page.

What to copy onto the cable line

  • Part: 82842 or 89842, from the sheet opened November 5, 2026.
  • Pairs: 2 of 24 AWG 7x32, white/blue and white/orange.
  • Jacket: PVC at 0.273 in, or FEP at 0.345 in.
  • Insulation diameter: 0.062 in, or 0.070 in.
  • Impedance: 120 Ohm. Current: 3.2 A at 25°C, or 4 A at 25°C.
  • Shield DCR: 2.4 Ohm/1000ft, or 3.1 Ohm/1000ft.
  • Temperature: UL 75°C and 0°C to +75°C, or UL 200°C and -70°C to +200°C.
  • Listing: 300 V (CMP). Non-plenum number on both plenum sheets: 9842.

82842 or 89842 note

Name the two-pair CMP jacket. Diameter and current change with the jacket on these sheets.

This prepares a request. It does not send one.

Questions these sheets answer

Does the two-pair FEP jacket keep 3.2 A?

82842 prints 3.2 A per conductor at 25°C, as of November 5, 2026. 89842 prints 4 A per conductor at 25°C. On the one-pair CMP sheets, both jackets list 4 A. These two-pair sheets do not share one current.

Does 0.273 in carry over to 89842?

82842's jacket is 0.273 in, as of November 5, 2026. 89842's jacket is 0.345 in. Insulation diameter is 0.062 in on 82842 and 0.070 in on 89842.

Does 89842's non-plenum cell print 9841ZH?

89842's non-plenum-number cell prints 9842, as of November 5, 2026. 82842's cell also prints 9842. The 9841ZH string is on 9842's own non-plenum cell, and that 9841ZH sheet was not opened.

Sources

Jacket, current, temperature, and the non-plenum cells are from the Belden 82842 and 89842 technical data sheets. The plenum-number cell that names both parts is from the Belden 9842 technical data sheet. All three were opened November 5, 2026. 9841ZH was not opened.