Raychem BPTM vs BBIT: Voltage Class and Clearance

Use BPTM when the sheet title is 25 kV and the bar is inside 6.5 mm to 220 mm. Use BBIT when the sheet title is 36 kV and the bar is inside 11 mm to 125 mm.

Rust Belt Industrials · October 23, 2026 · 7 min read

On this page

Use TE Raychem BPTM when the drawing follows data sheet EPP-0608, whose title is voltage class 25 kV for application diameters 6.5 mm to 220 mm. On that sheet's round-bar clearance table, opened October 23, 2026, 12 kV is 55 mm phase to phase and 65 mm phase to ground. Use TE Raychem BBIT when the drawing follows EPP-0607, whose title is voltage class 36 kV for application diameters 11 mm to 125 mm. On BBIT's round-bar table the same 12 kV clearance is 30 mm phase to phase and 40 mm phase to ground. A bar that sits inside both diameter ranges follows the voltage class named on the drawing. Both sheets say the user still tests the clearance.

The sheet title is the voltage class

EPP-0608 titles BPTM as voltage class 25 kV. EPP-0607 titles BBIT as voltage class 36 kV. The TE family listing opened the same day describes this tubing group as protection up to 72 kV, and its voltage-class filter offers bounds of 25 kV, 36 kV, and 72 kV. Order BPTM against the 25 kV title and BBIT against the 36 kV title. The 72 kV sentence is the group overview. It does not replace either sheet title. The epoxy and BBIT page is the comparison with powder applied after fabrication. This page stays with the two heat-shrink sheets.

BPTM's clearance table still includes a 36 kV row: 150 mm phase to phase and 205 mm phase to ground on the round-bar table, and 200 mm phase to phase and 285 mm phase to ground on the rectangular table. That row is the clearance at 36 kV on the BPTM sheet. It does not change the sheet title from 25 kV to 36 kV. Use the row whose rated voltage matches the drawing, and keep the product name with the title.

Clearances at 12 kV and 36 kV

Both sheets derive the clearance tables from BIL, AC withstand, DC withstand, and discharge-extinction tests. Both say these clearances should not be adopted without testing by the user, and that sharp electrodes and unusual geometries may require wider clearances. IEC 71-2 air clearance is the right-hand column. At 12 kV and at 36 kV that IEC column is 120 mm and 320 mm on both sheets, for round and rectangular bars. The phase-to-phase and phase-to-ground columns are the tubing clearances, and they are wider on BPTM than on BBIT at the same rated voltage.

Round and rectangular clearances from EPP-0608 (BPTM) and EPP-0607 (BBIT), opened October 23, 2026. The sheets say the user still tests the geometry.
Bar and voltageBPTM phase to phaseBPTM phase to groundBBIT phase to phaseBBIT phase to ground
Round, 12 kV55 mm65 mm30 mm40 mm
Round, 36 kV150 mm205 mm100 mm160 mm
Rectangular, 12 kV65 mm75 mm35 mm45 mm
Rectangular, 36 kV200 mm285 mm140 mm190 mm

The other rated-voltage rows are on the sheets. BPTM round is 70 mm phase to phase and 85 mm phase to ground at 17.5 kV, and 95 mm and 125 mm at 24 kV. BPTM rectangular is 85 mm and 105 mm at 17.5 kV, and 115 mm and 150 mm at 24 kV. BBIT round is 45 mm and 60 mm at 17.5 kV, and 60 mm and 90 mm at 24 kV. BBIT rectangular is 55 mm and 65 mm at 17.5 kV, and 70 mm and 100 mm at 24 kV. IEC 71-2 air clearance on both sheets is 160 mm at 17.5 kV and 220 mm at 24 kV.

Which ordering description covers the bar

BPTM's selection table, as of October 23, 2026, lists supplied inside diameter as H minimum and recovered inside diameter as h maximum. Wall thickness is W minimum as supplied and w maximum after free recovery. The note says to fit the larger size if two sizes fit. The rows below are the ones whose supplied and recovered inside diameters match the numbers in the ordering description. One ordering description on the sheet, BPTM-175/70-A/U-4, printed a supplied inside diameter that did not match 175, so that row is left off this table.

BPTM size rows from EPP-0608 whose inside diameters match the ordering description. Opened October 23, 2026. Dimensions are millimeters.
Ordering descriptionRectangular L+TRound diameterInside diameter supplied to recoveredWall supplied min to recovered max
BPTM-15/6-A/U-412 to 186.5 to 1215 to 61.1 to 1.90
BPTM-30/12-A/U-422 to 3813.5 to 2530 to 121.1 to 2.20
BPTM-50/20-A/U-436 to 6522 to 4350 to 201.1 to 2.35
BPTM-75/30-A/U-455 to 9533 to 6375 to 301.1 to 2.35
BPTM-100/40-A/U-470 to 13044 to 86100 to 401.1 to 2.35
BPTM-120/50-A/U-490 to 16555 to 105120 to 501.3 to 2.80
BPTM-205/110-A/U-4200 to 276127 to 190205 to 1101.3 to 2.80
BPTM-235/130-A/U-4235 to 315150 to 220235 to 1301.5 to 3.10

BBIT's selection table uses a different wall column. Supplied wall is nominal, 1.6 mm on every row opened October 23, 2026, and recovered wall is a minimum of 3.6 mm on every row. Round diameters run from 11 mm to 20 mm on BBIT-25/10-A/U-4 through 85 mm to 125 mm on BBIT-175/80-A/U-4. Rectangular L+T on those same rows runs from 17 mm to 28 mm through 133 mm to 196 mm. A round bar of 8 mm is inside BPTM-15/6-A/U-4 and below BBIT's 11 mm minimum. A round bar of 15 mm is inside BPTM-30/12-A/U-4 and also inside BBIT-25/10-A/U-4. Diameter overlap is why the voltage-class title still has to be on the request.

BPTM's readable recovery limits are a maximum longitudinal change after free recovery of +5% and -10%, and a maximum eccentricity as supplied of 40%. BBIT prints a maximum longitudinal change after free recovery of ±5% and a maximum eccentricity as supplied of 35%. The BPTM note also says to fit the larger size if two sizes fit, which is the same instruction BBIT prints.

Temperature and dielectric lines that stay with each sheet

BPTM thermal endurance is 105°C minimum to IEC 216. BBIT thermal endurance is 125°C minimum to IEC 216, also printed as 257°F minimum. Low-temperature flexibility on both sheets is no cracking after 4 hours at -40°C. BPTM can be stored indefinitely at temperatures up to 50°C. That storage line is on the BPTM sheet.

Dielectric strength on both sheets includes 180 kV/cm minimum at 2 mm, 150 kV/cm minimum at 2.5 mm, and 120 kV/cm at 3 mm. BBIT also prints 350 kV/cm minimum at 1.00 mm, which is 889 V/mil minimum at 0.04 inch. The BPTM specification table opened today lists the 2 mm, 2.5 mm, and 3 mm lines and does not show that 1.00 mm line. Keep each volts-per-thickness figure with the sheet that prints it. The epoxy comparison uses Storm's about 800 volts per mil at a 10 mil minimum, which is a third sentence.

What to name on the insulation line

  • Series and sheet: BPTM, EPP-0608, 25 kV title, or BBIT, EPP-0607, 36 kV title.
  • Ordering description from the size row, including BPTM-15/6-A/U-4 or BBIT-25/10-A/U-4 when that row is the one that fits.
  • Bar shape and the millimeter size matched to that row.
  • Rated voltage and the phase-to-phase and phase-to-ground cells from that sheet's round or rectangular table.
  • Recovered wall column as labeled: BPTM w maximum, or BBIT w minimum of 3.6 mm.
  • Faces that stay bare. Tubing over a joint is a different instruction from a plated contact face.

BPTM or BBIT note

Copy the sheet title, the ordering description, and the clearance row for the bar.

This prepares a request. It does not send one.

Questions the two tubing sheets answer

Does a 25 kV title use the BBIT 12 kV clearance?

BPTM's round-bar 12 kV clearance is 55 mm phase to phase. BBIT's round-bar 12 kV clearance is 30 mm phase to phase. The IEC 71-2 column is 120 mm on both. Copy the pair that belongs to the sheet named on the request.

Does BPTM's 36 kV clearance row make the tube a 36 kV part?

The BPTM title remains voltage class 25 kV. The 36 kV row is one line in the clearance table. A drawing that requires the 36 kV title uses BBIT, whose application range stops at 125 mm.

Does the family page's 72 kV line pick the tube?

The family listing overview says the tubing group provides protection up to 72 kV. EPP-0608 and EPP-0607 are the titles to order against. An HTIT sheet was linked from that listing and was not used for the clearances on this page.

Sources

BPTM voltage class, application range, clearances, size rows, wall columns, thermal endurance, storage, dielectric lines, longitudinal change, and eccentricity are from EPP-0608. BBIT voltage class, application range, clearances, wall, thermal endurance, dielectric lines, longitudinal change, and eccentricity are from EPP-0607. The 72 kV overview and the voltage-class filter are from the TE family listing. All three were opened October 23, 2026. One BPTM size row whose inside diameter did not match its ordering description was left out.