Power connections
Raychem HTIT: 36 kV Spacing or 72 kV Spacing
On the HTIT brochure, a round bar at 36 kV uses 100 mm phase to phase. The same shape at 72 kV uses 250 mm.
On this page
Use the HTIT size whose bar range contains the drawing, then use the clearance row for the specified voltage on the GVK Raychem HTIT brochure opened October 28, 2026. For a round bar at 36 kV that brochure lists 100 mm (3.94 in) phase to phase and 160 mm (6.30 in) phase to ground. For a round bar at 72 kV it lists 250 mm (9.84 in) phase to phase and 330 mm (12.99 in) phase to ground. Recovered wall thickness is 5.2 mm minimum on HTIT-44/18-A/U-4 and HTIT-65/27-A/U-4, and 5.1 mm minimum on HTIT-95/43-A/U-4. BPTM at 25 kV and BBIT at 36 kV are separate sheets, on the clearance page. This page uses the HTIT brochure.
Three ordering descriptions cover the bar ranges on the brochure
The product-selection table prints three ordering descriptions. HTIT-44/18-A/U-4 covers rectangular bars with L + T from 33 mm (1.30 in) to 62 mm (2.44 in), and round bars from 21 mm (0.83 in) to 40 mm (1.57 in). HTIT-65/27-A/U-4 covers rectangular bars from 48 mm (1.89 in) to 92 mm (3.62 in), and round bars from 31 mm (1.22 in) to 59 mm (2.32 in). HTIT-95/43-A/U-4 covers rectangular bars from 77 mm (3.03 in) to 135 mm (5.31 in), and round bars from 49 mm (1.93 in) to 86 mm (3.39 in). The brochure says to fit the larger size of HTIT if two sizes fit the application.
The ordering table uses H for the supplied inside diameter and h for the recovered inside diameter. HTIT-44/18-A/U-4 is 44 mm (1.73 in) supplied and 18 mm (0.71 in) recovered. HTIT-65/27-A/U-4 is 65 mm (2.56 in) supplied and 27 mm (1.06 in) recovered. HTIT-95/43-A/U-4 is 95 mm (3.74 in) supplied and 43 mm (1.69 in) recovered. The note under the table says W and H are as supplied, and w and h are after free recovery.
| Ordering description | Supplied ID | Recovered ID | Supplied wall, nominal | Recovered wall, minimum |
|---|---|---|---|---|
| HTIT-44/18-A/U-4 | 44 mm | 18 mm | 2.3 mm | 5.2 mm |
| HTIT-65/27-A/U-4 | 65 mm | 27 mm | 2.3 mm | 5.2 mm |
| HTIT-95/43-A/U-4 | 95 mm | 43 mm | 2.2 mm | 5.1 mm |
The brochure's opening paragraph says the tubes have an extra-thick wall of 5.1 to 5.2 mm. That range matches the recovered-wall minimums in the table. Supplied wall is the thinner nominal, 2.3 mm or 2.2 mm. Maximum longitudinal change after free recovery is ±5%. Maximum eccentricity is 35% as supplied and 15% after free recovery.
Each specified voltage has its own spacing row
The clearance table splits round bars from rectangular bars. The IEC 60071 air-clearance column is the same for both shapes at a given voltage: 380 mm (14.96 in) at 36 kV, 480 mm (18.90 in) at 52 kV, and 630 mm (24.80 in) at 72 kV. The phase-to-phase and phase-to-ground columns are shorter than that air-clearance column on every row. The brochure describes those shorter columns as the spacing the tube is for, in confined spaces on circular and rectangular copper or aluminum busbars, indoors or outdoors.
| Bar | Specified voltage | Phase to phase | Phase to ground | IEC 60071 air clearance |
|---|---|---|---|---|
| Round | 36 kV | 100 mm (3.94 in) | 160 mm (6.30 in) | 380 mm (14.96 in) |
| Round | 52 kV | 115 mm (4.54 in) | 170 mm (6.69 in) | 480 mm (18.90 in) |
| Round | 72 kV | 250 mm (9.84 in) | 330 mm (12.99 in) | 630 mm (24.80 in) |
| Rectangular | 36 kV | 95 mm (3.74 in) | 110 mm (4.33 in) | 380 mm (14.96 in) |
| Rectangular | 52 kV | 150 mm (5.91 in) | 240 mm (9.45 in) | 480 mm (18.90 in) |
| Rectangular | 72 kV | 290 mm (11.42 in) | 410 mm (16.14 in) | 630 mm (24.80 in) |
A rectangular bar at 36 kV is 95 mm phase to phase, which is 5 mm under the round-bar cell at the same voltage. At 72 kV the rectangular cell is 290 mm phase to phase, which is 40 mm over the round-bar cell. The shape on the drawing picks the row. The voltage picks the column pair.
Material tests printed under the HTIT heading
Thermal endurance is IEC 60216, 125°C minimum (257°F minimum). Low-temperature flexibility is ASTM D2671 procedure C, no cracking after 4 hours at -40°C (-40°F). Dielectric strength is ASTM D149: 350 kV/cm minimum at 1.00 mm, 180 kV/cm minimum at 2.00 mm, 150 kV/cm minimum at 2.50 mm, and 120 kV/cm minimum at 3.00 mm. Inclined-tracking rows name IEC 60587 and ASTM D2303 and list no tracking or erosion, 1 hour at 2.5 kV, and 1 hour at 2.75 kV. Flammability names ANSI C37.20/IEEE-27, no flame conveyance, 60 seconds maximum. Smoke index names NES 711, less than 120.
The GVK file footer reads EPP-4377-DDS-8/24, as of the copy opened October 28, 2026. The TE document-delivery copy of EPP-4377, opened the same day, prints the same three ordering descriptions, the same recovered-wall minimums, and the same 36 kV, 52 kV, and 72 kV spacing rows. Both copies print 2.3 (0.90) and 2.2 (0.90) in the supplied-wall cells. The wall thickness on this page stays the millimeter figure: 2.3 mm, 2.3 mm, and 2.2 mm nominal. The GVK file says installation instructions EPP-3264 and a material safety data sheet are available on request.
What to copy onto the insulation line
- Ordering description, such as HTIT-65/27-A/U-4, from the brochure opened October 28, 2026.
- Round or rectangular, and the bar dimension that falls inside that row.
- Specified voltage: 36 kV, 52 kV, or 72 kV.
- Phase-to-phase and phase-to-ground spacing from that row.
- Recovered wall minimum for that ordering description: 5.2 mm or 5.1 mm.
- The larger size, if two ordering descriptions both fit.
Questions the brochure table answers
Is the 36 kV row the same for round and rectangular bar?
Round bar at 36 kV is 100 mm phase to phase and 160 mm phase to ground. Rectangular bar at 36 kV is 95 mm and 110 mm. The IEC 60071 air clearance on both rows is 380 mm.
Which wall thickness is the 5.1 to 5.2 mm line?
The opening paragraph's 5.1 to 5.2 mm matches the recovered-wall minimums. Supplied wall on the same rows is 2.2 mm or 2.3 mm nominal.
Does this brochure replace the BBIT sheet?
BBIT clearances stay on the BBIT sheet. This brochure's 36 kV row is an HTIT row, with 100 mm phase to phase on a round bar. The BPTM and BBIT page is the place for those two sheet titles.
Sources
Sizes, inside diameters, wall thickness, clearances, eccentricity, longitudinal change, and the material-test rows are from the GVK Raychem HTIT brochure opened October 28, 2026. The same size and clearance rows are on TE sheet EPP-4377, opened the same day. Wall thickness is cited in millimeters. The inch figures printed beside the supplied-wall millimeter cells were not converted.