Power connections
Copper Busbar Bend Radius or Aluminum
For a 90° bend, Storm's fabrication note sets a typical copper radius equal to the thickness and a typical aluminum radius at 1.5 times the thickness.
On this page
For a 90° bend in rigid bar, use a radius equal to the thickness when the bar is copper, and use 1.5 times the thickness when the bar is aluminum. Storm's fabrication design guide v2.0, opened November 11, 2026, prints those two lines as the typical radius and says to specify the radius as a reference dimension, or with a generous tolerance, so the shop can use standard tooling. A flexible insulated bus on Storm's 2020 guideline is a different rule: the bend cell prints reference dimensions only, 90° or less, a spatial allowance of at least 3 times the product width, and a consistent bend radius. It does not print radius equal to thickness. Alloy and temper for a rigid copper bar are on the C110 and C102 page. The fabrication request that carries the radius is the custom copper page.
The 90° rule is copper at one thickness, aluminum at 1.5 thicknesses
The guide groups the radius rule under formability, fatigue life, and tooling. The two bullets are the numeric rule: copper typical radius equals thickness, and aluminum typical radius equals 1.5 times thickness. A drawing that already names the thickness uses that thickness as the copper radius, or 1.5 times that thickness as the aluminum radius. The same paragraph says a reference dimension or a generous tolerance lets Storm use standard tooling. A tight tolerance on the radius is a different instruction from that reference dimension.
The material block on the same guide, opened November 11, 2026, prints a typical callout of copper C110 to ASTM B152 or ASTM B187, temper H00 to H02, and aluminum 1100 to ASTM B209 or 6101 to ASTM B317. It says unprocessed sheet and bar can be expected to hold 0.005 inch per inch flatness and 125 microinch (3.2 micrometers) or better surface roughness, and that this finish is enough for most busbar applications. It also says the drawing should allow both sheet and bar, and a range of tempers, so the shop can choose the route. The radius rule still follows the metal: copper or aluminum.
The same note prints two minimum edge radii
Storm deburrs parts unless the customer instructs otherwise, and the guide says that practice does not normally need a drawing callout because it is hard to measure directly. The numeric edge lines are separate from deburr. As of November 11, 2026, the typical minimum edge radius for uninsulated parts is R.005 inch, and the typical minimum edge radius for insulated parts is R.020 inch. Sharp external corners, in the geometry section, can cut insulation or a wiring harness. The guide's recommendation is a radius on internal and external corners unless a sharp feature is required for fit. It says a sharp internal corner can create an electrical hot spot.
Bends near a free edge are described without a minimum distance. The guide says a bend that is too close to the edge can roll or tear, and that the formed section can run hotter if the cross section is reduced. The instruction is to place the bend far enough from the edge to keep the full cross section through the bend. A hole or other cut close to a bend can distort, and the guide's practice is to move the feature away from the bend or to change a round hole into a slot that continues through the formed region. Short legs can be bent long and then machined, or made with special tooling.
A flexible insulated bus uses the 2020 bend cell
The flexible insulated bus bar design guideline, opened November 11, 2026, puts bends, twists, and radii in one cell. The words in that cell are reference dimensions only, 90° or less, a spatial allowance of at least 3 times the product width, and a consistent bend radius on the part. The rigid copper and aluminum radius rules stay on the v2.0 fabrication note. The insulation row of the same 2020 guideline prints plus or minus 0.06 inch on flat bars, a minimum of 0.50 inch from the insulation to a bend or twist, and a handling line: do not handle the material at temperatures of 30°F or less. A powder-coated rigid bar has a hole-diameter rule on the enamel and powder page.
The formed view governs. The flat blank is a reference
The fabrication guide says different tools need different bend allowances, so one flat pattern is not the pattern for every press. It asks for formed views, and it says any flat blank on the drawing should be reference only, so the shop can develop the flat from the tools it will use. Dimensioning to a theoretical intersection can be hard to measure by hand. The guide's point is that the drawing has to support inspection on the floor. Nested forms, where one bent bar fits inside another, need clearance so the bars go together without forcing.
What to copy onto the bend line
- Bar: rigid copper, rigid aluminum, or the flexible insulated bus, as of the notes opened November 11, 2026.
- Rigid copper, 90°: typical radius equal to the thickness. Call it a reference dimension, or give it a generous tolerance, when the shop is to use standard tooling.
- Rigid aluminum, 90°: typical radius equal to 1.5 times the thickness, on the same terms.
- Material callout from the fabrication note: C110 to ASTM B152 or ASTM B187, H00 to H02, or aluminum 1100 to ASTM B209, or 6101 to ASTM B317.
- Edge: R.005 inch uninsulated, or R.020 inch insulated, when the drawing needs the note's minimum.
- Flexible insulated bus: the 2020 bend cell, including a spatial allowance of at least 3 times the product width, and the 30°F handling line.
- Flat pattern: reference. The formed view is the one the note asks the shop to build.
Questions the fabrication notes answer
What radius does a 90° copper bend use?
Storm's v2.0 note, as of November 11, 2026, sets the typical copper radius equal to the thickness. The typical aluminum radius on the same line is 1.5 times the thickness.
Which edge radius is the insulated bar?
R.020 inch, as of November 11, 2026. The uninsulated minimum on the same note is R.005 inch. Deburr, unless the customer says otherwise, is the shop practice and is separate from those two radii.
Does the flexible insulated bus use the copper thickness rule?
The 2020 guideline's bend cell does not print radius equal to thickness. It prints reference dimensions, 90° or less, a spatial allowance of at least 3 times the product width, and a consistent bend radius.
Sources
The copper and aluminum radius lines, the edge radii, the material callout, and the flat-blank instruction are from Storm's fabrication design guide v2.0. The flexible bend cell, the 0.50 inch insulation clearance, and the 30°F handling line are from the flexible insulated bus bar design guideline. Both were opened November 11, 2026.