nVent Flexibar: IEC Rise Current or UL Rise Current

Use the IEC 50°C cell when that table is the one on the drawing. For 5 x 32 x 1 mm the IEC cell is 640 A and the UL 50°C cell is 671 A.

Rust Belt Industrials · October 23, 2026 · 6 min read

On this page

Use the IEC ampacity table in the nVent ERIFLEX Flexibar brochure when the drawing names that table. For 5 layers of 32 mm by 1 mm, 160 mm², the IEC 50°C rise cell is 640 A, opened October 23, 2026. Use the UL ampacity table when the drawing names that table. The same 5 x 32 x 1 mm section lists 671 A at a 50°C rise on the UL table, and the typical-application column on that UL row reads 400 A while the IEC row reads 630 A. The construction page gives the family span and says to use the product table. This page is that table for the sections below.

The brochure prints an IEC table and a UL table

The IEC table columns used here are a 20°C rise through a 70°C rise, in 10°C steps, plus three parallel-bar coefficients. The UL table columns that line up with the data rows are a 20°C rise, an NEC 310-16 60°C cell, a 35°C rise, a 40°C rise, an NEC 310-16 75°C cell, a 50°C rise, an NEC 310-16 90°C cell, a 65°C rise, and a 70°C rise, then the coefficients. A 30°C rise is an IEC column. The UL header that matches these rows does not have a 30°C cell. Copy the column the drawing names.

The brochure says the rise is the temperature of the conductor minus the internal temperature of the panel, and that the calculation does not take heat dissipation from the switchgear into account. It also says to respect the instructions of the electrical device manufacturer. The rise current is the cell in the rise column. The left-hand typical-application label is a different cell, and on these rows it is not equal to the 50°C current.

Flexibar sections that appear in both the IEC and UL tables of P1349W-USEN, opened October 23, 2026. Currents are amperes.
SectionIEC 30°CIEC 50°CUL 20°CUL 50°CTypical rating, IEC row / UL row
3 x 9 x 0.8 mm, 21.6 mm²104 A134 A101 A167 A125 A / 125 A
2 x 15.5 x 0.8 mm, 24.8 mm²165 A212 A121 A201 A125 A / 125 A
6 x 9 x 0.8 mm, 43.2 mm²190 A245 A153 A255 A125 A / 125 A
5 x 32 x 1 mm, 160 mm²496 A640 A405 A671 A630 A / 400 A

How to read one section

Take 3 x 9 mm x 0.8 mm, 21.6 mm². The IEC row, labeled 125 A in the typical-application column, lists 85 A at 20°C, 104 A at 30°C, 120 A at 40°C, 134 A at 50°C, 147 A at 60°C, and 158 A at 70°C. The UL row for the same layers lists 101 A at 20°C, 148 A at 40°C, and 167 A at 50°C. The NEC 310-16 cells on that UL row are 126 A in the 60°C column, 158 A in the 75°C column, and 185 A in the 90°C column. An IEC 30°C current of 104 A is not a UL current for this section, because the UL table does not print a 30°C column on these rows.

The 2 x 15.5 x 0.8 mm section is 24.8 mm². IEC lists 134 A at 20°C, 165 A at 30°C, and 212 A at 50°C. UL lists 121 A at 20°C and 201 A at 50°C. Both rows carry a 125 A typical-application label. The label is shared. The rise cells are not. A request that says only 125 A has not chosen the section or the table.

The 6 x 9 x 0.8 mm section is 43.2 mm² and also carries the 125 A typical label on both tables. IEC lists 155 A at 20°C, 190 A at 30°C, and 245 A at 50°C. UL lists 153 A at 20°C and 255 A at 50°C. Three different builds share the 125 A label and publish three different 30°C currents on the IEC table: 104 A, 165 A, and 190 A.

Parallel bars use the coefficient on that row

The brochure's parallel example is 5 x 32 x 1, 160 mm², at a 50°C rise: 640 A on the IEC table. That matches the IEC row above. The same row prints current coefficients 1.72, 2.25, and 2.93. The brochure then prints two bars as 640 A x 1.72 = 1100 A, three bars as 640 A x 2.25 = 1440 A, and four bars as 640 A x 2.93 = 1875 A. Those products are the example. Later rows in the same IEC table print other coefficients, including 1.65, 2.12, and 2.70, and 1.60, 2.02, and 2.40. Copy the coefficient from the row you are using.

On the UL table the same 5 x 32 x 1 mm section lists 405 A at 20°C and 671 A at 50°C, with a typical-application label of 400 A. The IEC typical-application label on that geometry is 630 A. Parallel arithmetic that starts from 640 A is the IEC 50°C example. A UL 50°C start is 671 A, and this page does not multiply 671 by the IEC example.

Which column matches the drawing

Name the table first, IEC or UL. Then name the rise. A drawing that says 30°C uses the IEC 30°C cell, because that is the column the IEC table prints. A drawing that says 50°C still has to say which table, because 5 x 32 x 1 mm is 640 A on IEC and 671 A on UL. A drawing that cites NEC 310-16 uses the UL cell with that insulation-temperature heading: 60°C, 75°C, or 90°C. Those NEC cells are not rise columns. On the 21.6 mm² UL row they are 126 A, 158 A, and 185 A.

Rigid C11000 bar current for a named rise is a different chart, on the ampacity page. Flexibar currents stay in the Flexibar brochure. The brochure says to select Flexibar according to the terminal width of the equipment being connected, so the layer width still has to match the terminal, not only the ampere cell.

What to copy onto the Flexibar line

  • Table: IEC or UL, from the brochure opened October 23, 2026.
  • Layers, width, and thickness, such as 5 x 32 x 1 mm, and the section in mm².
  • Rise column, or the NEC 310-16 heading if that is the cell.
  • Current printed in that cell. For IEC 50°C on 5 x 32 x 1 mm, 640 A.
  • Parallel count and the coefficient printed on that row, if more than one bar shares the phase.
  • Terminal width the brochure says to match.

Flexibar current note

Copy the table, the section, and the rise cell. This file does not size the panel.

This prepares a request. It does not send one.

Questions the brochure tables answer

Is every row marked 125 A able to carry 125 A at 30°C?

On the IEC table, 3 x 9 x 0.8 mm lists 104 A at 30°C and is still marked 125 A in the typical-application column. The 30°C cell is the current for that rise. The 125 A label does not replace it.

Do IEC and UL print the same 50°C current?

For 5 x 32 x 1 mm, IEC prints 640 A and UL prints 671 A. For 3 x 9 x 0.8 mm, IEC prints 134 A and UL prints 167 A. Use the table named on the drawing.

Can the 1.72 coefficient be reused on every section?

The 5 x 32 x 1 mm IEC row prints 1.72 for two bars. Other IEC rows print 1.65 or 1.60 in that position. The coefficient comes from the row.

Sources

Rise currents, typical-application labels, NEC cells, and parallel coefficients are from the IEC and UL ampacity tables in nVent brochure P1349W-USEN. The 640 A parallel example is the brochure's own example for 5 x 32 x 1 at 50°C on the IEC table, and that base current matches the IEC row. The rise definition is the brochure's note that conductor temperature minus internal panel temperature does not include switchgear heat dissipation. The brochure was opened October 23, 2026.