Skip to the guide

Power connections

nVent Flexibar or IBS/IBSB Advanced Insulated Braid

Use Flexibar from 27 mm² and 125 A through 1200 mm² and 2,800 A. Use IBS/IBSB Advanced from 25 mm² and 80 A through 240 mm² and 700 A.

Rust Belt Industrials · October 24, 2026 · 5 min read

On this page

Use nVent ERIFLEX Flexibar when the connection is a stack of thin electrolytic tinned copper laminates. As of October 24, 2026, the Flexibar page lists 27 mm² up to 1200 mm² and 125 A to 2800 A. Use IBS/IBSB Advanced when the connection is a woven electrolytic-copper braid for a molded-case breaker front terminal. As of the same day, that page lists 25 to 240 mm² (49.34 to 273.65 kcmil), 80 to 700 A, and lengths from 230 to 1,030 mm (9.06 in to 40.55 in). A section above 240 mm², or a current above 700 A, is outside the IBS/IBSB span and still inside the Flexibar span when it is also at or under 1200 mm² and 2800 A. The construction page separates foil, expansion links, braid, and dielectric laminates. This page stays with these two nVent products.

One product is a laminate stack, and the other is a woven braid

The Flexibar page says the conductor is formed from multiple layers of thin electrolytic tinned copper, insulated with a high-resistance, self-extinguishing TPE compound that is halogen free and low smoke. The insulating sleeve is grooved on the inner surface. The page says that groove reduces the contact surface with the laminates to less than 20%. Every cross section on that page can be bent, folded, or twisted. Connections are made by punching and bolting directly through the copper laminates, by clamping the end, or by welding using nVent ERICO Cadweld. The page says there are no lugs to purchase or install.

The IBS/IBSB Advanced page says the conductor is formed by weaving high-quality electrolytic copper wire. It does not call that wire tinned. Integral pre-punched palms make the part ready to connect, and the page says the front-access terminals of molded-case breakers, including compact breakers, do not need angular connectors, spreaders, ring terminals, or extenders. The insulation is a high-resistance, low-smoke, halogen-free, flame-retardant thermoplastic. The page says the part is compliant with UL 94-V0 and a glow wire test at 960°C, and that the limiting oxygen index is 30%.

Spans printed on the two nVent pages opened October 24, 2026.
ItemFlexibarIBS/IBSB Advanced
BuildLayers of thin electrolytic tinned copperWoven electrolytic copper wire
Cross section27 mm² to 1200 mm²25 to 240 mm² (49.34 to 273.65 kcmil)
Current span125 A to 2800 A80 A to 700 A
Length on the pageFormed on site. A catalog length range is not in this family paragraph.230 to 1,030 mm (9.06 in to 40.55 in)
EndPunch and bolt, clamp, or CadweldIntegral pre-punched palms
Insulation namedSelf-extinguishing TPE, halogen free, low smoke, sleeve contact under 20%Halogen-free thermoplastic, UL 94-V0, glow wire 960°C, LOI 30%

The family span is not one rise cell

Flexibar 2800 A is the top of the family span on the product page. A drawing that names a rise column still uses the IEC or UL cell for that section, on the ampacity table page. IBS/IBSB Advanced lists 80 to 700 A as the range of the family. The page opened on October 24, 2026 did not print a temperature-rise table for one braid section. A request that says only 400 A has not chosen the product, because 400 A sits inside both spans.

Both pages say the parts are manufactured in an ISO 9001:2015 certified facility. Flexibar calls it a proprietary automated facility. IBS/IBSB Advanced calls it an automated facility. The certificate line is shared. The conductor construction is not.

Halogen-free language is printed on both pages, with extra test names on the braid

Flexibar describes the TPE as halogen free and low smoke. IBS/IBSB Advanced, on the page opened October 24, 2026, adds the test names. It says low smoke opacity is in accordance with IEC 61034-2 and UL 2885, and that the part does not contain halogens according to IEC 60754-1 and UL 2885. It lists enclosed spaces such as data centers, rail, hospitals, schools, submarines, and switchboards as examples. Flexibar's own page also says the insulation is halogen free and low smoke, without those IEC numbers in the paragraph opened the same day.

The IBS/IBSB page shows certification marks that include CSA, RoHS, UR, cUR, DNV GL, ABS, CE, and Bureau Veritas. The Flexibar family paragraph opened today does not list that same mark row. A mark on the braid page stays with the braid page.

What to copy onto the line

  • Product: Flexibar, or IBS/IBSB Advanced, from the page opened October 24, 2026.
  • Cross section. Flexibar is 27 mm² to 1200 mm². IBS/IBSB Advanced is 25 to 240 mm².
  • Current basis. Family span, or the IEC or UL rise cell when the part is Flexibar.
  • Length, when the part is IBS/IBSB Advanced: 230 to 1,030 mm on that page.
  • End: punched laminate, clamp, Cadweld, or a pre-punched braid palm.
  • Breaker brand only if the drawing already names it. The braid page says the part is compatible with all major molded-case brands and does not list the brands.

Flexibar or insulated braid note

Name the nVent product and the section or current from that product page.

This prepares a request. It does not send one.

Questions the two pages answer

Which product covers a current above 700 A?

The IBS/IBSB Advanced span stops at 700 A. The Flexibar span continues to 2800 A. Above 700 A, the family pages point to Flexibar, and the rise cell still comes from the Flexibar table for the section on the drawing.

Are both conductors described as tinned?

Flexibar says electrolytic tinned copper. IBS/IBSB Advanced says electrolytic copper wire. The braid page does not add the word tinned in the paragraph opened October 24, 2026.

Can the braid palm replace a punched Flexibar end?

The IBS/IBSB page describes pre-punched palms for breaker front terminals. The Flexibar page describes punching, clamping, or Cadweld on a laminate stack. The request names the end the drawing already uses.

Sources

Flexibar cross section, current, tinned copper, sleeve contact under 20%, and the three connection methods are from the Flexibar family page. IBS/IBSB cross section, kcmil equivalents, current, length, palms, UL 94-V0, glow wire, limiting oxygen index, and the halogen-free test names are from the IBS/IBSB Advanced page. Both were opened October 24, 2026.