PROFINET 4-Core Pair Colors: Yellow/Orange and White/Blue

PI assigns pair 1 to yellow and orange and pair 2 to white and blue. Beckhoff's Ethernet pin table uses those same pairs on pins 1-2 and 3-6.

Rust Belt Industrials · October 23, 2026 · 5 min read

On this page

On a 4-core PROFINET cable, pair 1 is yellow and orange and pair 2 is white and blue. That is the sentence on PI North America's copper-cable page, opened October 23, 2026. Beckhoff's EtherCAT wiring table, which it says is compatible with the Ethernet pin assignment in ISO/IEC 8802-3, uses the same pairs: pin 1 yellow TD+, pin 2 orange TD-, pin 3 white RD+, and pin 6 blue RD-. An 8-core PROFINET cable is a different list on the PI page: green, blue, orange, and brown, each with a white wire. The LAPP PROFINET Type A catalog page opened the same day prints a green jacket and does not list these core colors.

What PI prints for a 4-core cable

PI describes a typical PROFINET copper cable as a 4-core shielded cable, a star quad, and says 8-core cables have been specified for 1000 Mbit/s. The cores are always color-coded. In a 4-core cable, wire-pair-1 is yellow and orange and wire-pair-2 is white and blue. The cores in each pair sit diametrically opposite. The maximum distance between two endpoints on copper is 100 m. The page also repeats Type A for fixed installation, Type B for occasional motion or vibration, and Type C for continuous movement such as trailing chains. Those type letters are the subject of the type page. Jacket color does not choose the pair colors. The Type A catalog example opened today is green and still omits the core list.

Beckhoff's pin table uses the same two pairs

Beckhoff says the cable length between two EtherCAT devices must not exceed 100 m, and that EtherCAT devices should be connected with Ethernet cables of at least category 5 according to EN 50173 or ISO/IEC 11801. EtherCAT uses 4 wires for signal transfer. The pin table is:

Beckhoff EtherCAT wiring pin table, opened October 23, 2026. PI names the same color pairs and does not print these pin numbers.
PinConductor colorSignal on the Beckhoff table
1yellowTD+
2orangeTD-
3whiteRD+
6blueRD-

Yellow with orange is one pair on this table, on pins 1 and 2. White with blue is the other pair, on pins 3 and 6. That pairing matches PI's pair 1 and pair 2. PI's copper page does not print RJ45 pin numbers in the paragraph that names the colors. Beckhoff also says automatic cable detection allows a symmetric 1:1 cable or a cross-over cable between Beckhoff EtherCAT devices. A crossed cable still uses these colors. It changes which device pin a color lands on. The device sheet is the pin map for a PROFINET port. This table is the Beckhoff EtherCAT map, cited here because the color pairs are the same ones PI names.

The 8-core list is a second PI sentence

PI says 8-core PROFINET copper cables consist of 4 wire pairs, with green, blue, orange, and brown wires plus a corresponding white wire for each. Blue and orange appear in that 8-core list and also in the 4-core pairs. They are not one map. A 4-core cable uses yellow/orange and white/blue. An 8-core cable uses the four colors that each have a white mate. Beckhoff's 4-wire table does not describe the 8-core list. A request for 1000 Mbit/s should say 8-core and should list green, blue, orange, and brown, each with white, when the PI sentence is the one being followed.

A green jacket, and other ETHERLINE color codes

LAPP's PROFINET Type A page prints the outer sheath as green, based on RAL 6018, and an outdoor version as black, similar to RAL 9005. It does not print yellow, orange, white, or blue as core colors. Article 2170891 is the 6.3 mm green Type A row on the Type A comparison. The jacket can be green while the cores follow PI, and this catalog page does not prove the cores by itself.

A Lapp Tannehill datasheet for ETHERLINE 2-pair CAT.5/CAT.5e flexible cable, opened October 23, 2026, prints two color codes. Articles 2170886 and 2170901 are white, yellow, blue, and orange. Articles 2170283 and 2170284 are white/orange and orange, and white/green and green. Those four article numbers are not the Type A numbers 2170891, 2170893, 2170879, and 2170933. The white/orange and white/green code is a different pair list from PI's yellow/orange and white/blue. Characteristic impedance on that datasheet is 100 Ω ± 15 Ω. The sheet does not say which of white, yellow, blue, and orange form pair 1. Pair 1 as yellow and orange remains the PI sentence, agreed in pairing by the Beckhoff pin table.

What to write for the pairs

  • Core count: 4-core or 8-core.
  • 4-core pairs: pair 1 yellow and orange, pair 2 white and blue, from the PI page opened October 23, 2026.
  • 8-core: green, blue, orange, and brown, each with a white wire, if that PI sentence is the one in use.
  • Connector pin map from the device sheet. Beckhoff's table is pin 1 yellow, pin 2 orange, pin 3 white, pin 6 blue.
  • Jacket color as a separate field. Green does not select the pairs.
  • Article number when a catalog color code differs, such as 2170283.

PROFINET pair color note

Write the core count and the pair colors from the page you are using.

This prepares a request. It does not send one.

Questions these color pages answer

Does a green jacket mean the cores are green and white?

The LAPP Type A page prints a green sheath and does not print core colors. PI's 4-core pairs are yellow/orange and white/blue. The 8-core sentence is the one that includes a green wire, and that wire has its own white mate.

Is pin 3 orange?

On the Beckhoff table, pin 3 is white, RD+. Orange is pin 2, TD-. PI does not number the pins in the color paragraph. Use the device pin map when the port is not the Beckhoff table.

Can articles 2170283 and 2170284 be landed as yellow and orange?

Those two articles are printed as white/orange and orange, and white/green and green. That list is not PI's yellow and orange pair. A yellow/orange landing uses a cable whose color code is the PI pairs, or articles 2170886 and 2170901 if the four colors white, yellow, blue, and orange are the list that sheet prints and the pair grouping is taken from PI.

Sources

Pair 1, pair 2, the 8-core list, the 100 m copper distance, and the star-quad description are from PI North America. The pin colors, the 100 m EtherCAT limit, and the Cat5 sentence are from Beckhoff's wiring page. The green Type A sheath and the missing core list are from LAPP's Type A catalog page. The two alternate ETHERLINE color codes and the 100 Ω ± 15 Ω impedance are from the Lapp Tannehill flexible datasheet. All four were opened October 23, 2026.