Skip to the guide

Industrial networking

Beckhoff ZB9010 Fixed PVC or ZB9020 Drag-Chain PUR

Use ZB9010 for fixed green PVC with a solid conductor. Use ZB9020 for drag-chain green PUR with a 7 x 0.25 mm conductor. Both list 6.5 mm and AWG22.

Rust Belt Industrials · October 26, 2026 · 6 min read

On this page

Use Beckhoff ZB9010 when the EtherCAT cable is fixed installation. As of October 26, 2026, that sheet lists a PVC jacket, a solid conductor, cross-section 1 x 4 x 0.34 mm² (AWG22), and an outer diameter of 6.5 mm ± 0.2 mm (0.2559 in ± 0.0079 in). The moved bend is 7.5 times the outer diameter, and the fixed bend is 3 times. Use Beckhoff ZB9020 when the cable is drag-chain suitable. As of the same day, that sheet lists a PUR jacket, conductor construction 7 x 0.25 mm, the same cross-section 1 x 4 x 0.34 mm² (AWG 22), and the same outer diameter of 6.5 mm ± 0.2 mm. The drag-chain bend is 15 times the outer diameter. The wiring page names ZB9010 for fixed installation, CAT 5e, 4-core, and ZB9020 for drag chain, CAT 5e, 4-core. A yellow fixed PVC cable and an EtherCAT P drag-chain cable are a different pair, on the ZB7005 and ZB9013 page.

The wiring page names both, and the 100 m rule is separate

The EtherCAT wiring page opened October 26, 2026 says the cable length between two EtherCAT devices must not exceed 100 m, and that the cable should meet at least category 5 according to EN 50173 or ISO/IEC 11801. EtherCAT uses 4 wires. The pin table is pin 1 yellow TD+, pin 2 orange TD-, pin 3 white RD+, and pin 6 blue RD-. The suitable-cable list names ZB9010 and ZB9020. It does not name ZB9013 or ZB7005. Neither cable sheet prints 100 m as a cable length. Each sheet's length note is a tolerance of 2-3% on the ordered length. The 100 m sentence stays on the wiring page.

Solid PVC, or stranded PUR, at one diameter

As of October 26, 2026, ZB9010 cable structure is twisted shielded pair, conductor construction solid, jacket PVC, jacket color green, wire colors yellow, orange, white, and blue. Shielding is a braid of tinned copper wires, optical covering 90%. Weight is 67 kg/km (45.0 lb/1000 ft). ZB9020 cable structure is star quad, conductor construction 7 x 0.25 mm, conductor material copper, tinned, wire insulation PP, wall thickness 0.375 mm, jacket PUR, jacket color green, and the same four wire colors. Shielding is aluminum-clad foil and a braid of tinned copper wires, optical covering at least 85%. Weight is 61 kg/km (41.0 lb/1000 ft). Both are sold by the meter, and both list a 500 m put-up, ZB9010-R000 and ZB9020-R000.

The ZB9010 jacket print, as of October 26, 2026, includes the string 2x2x22AWG, plus CMG FT4 75°C, CAT 5E or PLTC SUN RES, and AWM 21694 600V. The cross-section cell is 1 x 4 x 0.34 mm² (AWG22). Copy the cross-section cell and record the jacket-print string. The ZB9020 jacket print says 22AWG, CMX 75°C, CAT 5E PATCH CABLE, and FRNC. It does not print 2x2. The ZB9020 cross-section cell is 1 x 4 x 0.34 mm² (AWG 22), with a space in AWG 22.

ZB9010 and ZB9020 rows from the sheets opened October 26, 2026.
ItemZB9010ZB9020
Use on the sheetFixed installationDrag-chain suitable
JacketPVC, greenPUR, green
ConductorSolid7 x 0.25 mm, tinned copper
Outer diameter6.5 mm ± 0.2 mm6.5 mm ± 0.2 mm
Cross-section cell1 x 4 x 0.34 mm² (AWG22)1 x 4 x 0.34 mm² (AWG 22)
Moved bend7.5 x outer diameter8 x outer diameter
Drag-chain bendNot printed15 x outer diameter
Fixed bend3 x outer diameter5 x outer diameter

100 Ohm on both, with different capacitance and insulation resistance

As of October 26, 2026, both sheets list rated voltage 600 V, operating voltage at most 125 V peak value and not for high-voltage purposes, characteristic impedance 100 Ω ± 15 Ω at 100 MHz, loop resistance at most 115 Ω/km, signal running time 5.3 ns/m, electrical parameters based on Cat.5, and test voltage at least 2000 V. ZB9010 mutual capacitance is 48 nF/km, with no frequency in that cell, and insulation resistance is at least 5 GΩ/km. ZB9020 mutual capacitance is 52 nF/km at 1 kHz, and insulation resistance is at least 500 MΩ/km. Those resistance cells use different units. Copy each one as printed. ZB9020 also prints shielding attenuation of at least 40 dB, unbalanced capacitance to ground of 1600 pF/km, differential impedance of 250 Ω/km, unbalanced resistance of 2%, and dielectric strength of 1000 V DC and 700 V AC for wire to wire and for wire to shield. ZB9010 does not print those five cells.

As of October 26, 2026, both attenuation tables print maximum insertion loss at 1, 4, 10, 16, 20, 31.25, 62.5, and 100 MHz. At 1 MHz the ZB9010 cell is 1.6 dB/100 m (0.5 dB/100 ft) and the ZB9020 cell is 2.1 dB/100 m (0.6 dB/100 ft). At 100 MHz the ZB9010 cell is 19.5 dB/100 m (5.9 dB/100 ft) and the ZB9020 cell is 21.3 dB/100 m (6.5 dB/100 ft). The sheets print the unit as db/100 m and db/100 ft. Near-end crosstalk at 100 MHz is 50.0 dB/100 m on both. UL file number E119100 is on both. ZB9020 approvals are UL, CMX according to UL 444. ZB9010's flame line is IEC 60332-1-2 and UL 1685 (CSA FT 4). ZB9020's flame line is the VW-1 flame test, UL 1581 section 1080, and IEC 60332-1-2.

Temperature, cycles, and torsion are on ZB9020

As of October 26, 2026, ZB9010 moved operation is -20°C to +60°C (-4°F to +140°F). Fixed installation and transport are -40°C to +75°C (-40°F to +167°F). The sheet does not print a cycle count, a travel distance, or a torsion angle. ZB9020 moved operation is -30°C to +80°C (-22°F to +176°F). Fixed installation is -40°C to +80°C (-40°F to +176°F). Maximum acceleration is 4 m/s², maximum speed is 4 m/s, maximum travel distance is 4.5 m, and maximum cycles are 3 million. Torsion is at most ± 30 °/m. UV resistance is yes. Oil resistance is according to DIN EN 60811-404, 7 times 24 h at 90°C. Halogen-free is yes. ZB9010 does not print a halogen-free cell. Sheet revision is 2.5 on ZB9010, with a 02/2025 copyright line, and 2.4 on ZB9020, with a 06/2023 copyright line.

What to copy onto the cable line

  • Part: ZB9010 or ZB9020, from the sheet opened October 26, 2026.
  • Use: fixed installation, or drag-chain suitable, matching the wiring-page list.
  • Jacket and diameter: PVC or PUR, green, 6.5 mm ± 0.2 mm.
  • Conductor: solid, or 7 x 0.25 mm tinned copper.
  • Cross-section cell: 1 x 4 x 0.34 mm² (AWG22) or (AWG 22). Record 2x2x22AWG only as the ZB9010 jacket print.
  • Bend: 7.5 x moved and 3 x fixed, or 8 x moved, 15 x in a chain, and 5 x fixed.

ZB9010 or ZB9020 note

Name fixed PVC or drag-chain PUR, and copy the bend cell you are using.

This prepares a request. It does not send one.

Questions these sheets answer

Does 6.5 mm mean the jackets match?

Both outer-diameter cells are 6.5 mm ± 0.2 mm, as of October 26, 2026. The jacket material is PVC or PUR, the conductor is solid or 7 x 0.25 mm, and the drag-chain bend is printed only on ZB9020. Diameter does not choose the motion.

Which ZB9010 construction string goes on the request?

Copy the cross-section cell, 1 x 4 x 0.34 mm² (AWG22), as of October 26, 2026. Record that the jacket print still includes 2x2x22AWG. The sheet does not retire either string.

Does the wiring page's 100 m rule come from the cable sheet?

The 100 m limit is the distance between two EtherCAT devices on the wiring page, opened October 26, 2026. ZB9010 and ZB9020 print a 2-3% length tolerance. They do not print 100 m.

Sources

Jacket, conductor, diameter, bend, capacitance, and temperature are from the Beckhoff ZB9010 and ZB9020 data sheets. The suitable-cable names and the 100 m link limit are from the Beckhoff EtherCAT wiring page. All three were opened October 26, 2026.