Skip to the guide

Industrial networking

Belden 3131A at 120 Ohm or 3132A at 100 Ohm

Use 3131A for the PVC non-plenum coax at 120 Ohm and 75°C. Use 3132A for the PVDF plenum coax at 100 Ohm and 150°C. Each sheet names the other as its pair.

Rust Belt Industrials · October 28, 2026 · 6 min read

On this page

Use Belden 3131A when the ControlBus coax is the non-plenum PVC number. As of October 28, 2026, that sheet lists 120 Ohm ± 3 Ohm, a PVC jacket of 0.301 in, UL temperature 75°C, and operating temperature -30°C to +75°C. Use Belden 3132A when the coax is the plenum PVDF number. As of the same day, that sheet lists 100 Ohm ± 3 Ohm, a PVDF jacket of 0.274 in, UL temperature 150°C, and operating temperature -20°C to +150°C. 3131A's plenum-number cell is 3132A. 3132A's non-plenum-number cell is 3131A. The two sheets point at each other, and the impedance cells are 120 Ohm and 100 Ohm. The 75 Ohm plenum coax named from 3092A is 3093A, on the 3093A and 3132A page.

Each sheet names the other, and the Ohm cells differ

As of October 28, 2026, 3131A prints Plenum (Y/N) No and plenum number 3132A. 3132A prints Plenum (Y/N) Yes and non-plenum number 3131A. Both suitable-application cells name harsh environment, factory automation, ControlNet, and Modbus II. A request that starts from the non-plenum cell on 3132A still copies 120 Ohm from the 3131A sheet. A request that starts from the plenum cell on 3131A still copies 100 Ohm from the 3132A sheet. The part number in the cross-reference cell does not carry the impedance across.

18 AWG solid BCCS, PVC at 0.301 in or PVDF at 0.274 in

As of October 28, 2026, both sheets list one 18 AWG solid bare-copper-covered-steel conductor with a nominal diameter of 0.04 in, and one coax. Neither diameter cell prints a millimeter. 3131A's product description says PO insulation. The insulation cell on that sheet says PE, polyethylene, foam, nominal diameter 0.18 in, and the insulation note says gas injected. 3132A's description and insulation cell both say FEP, and the insulation cell adds foam, nominal diameter 0.17 in. Copy the insulation cell with the description line when the 3131A row is the one on the request. The shield is four layers on both sheets: a Duofoil tri-laminate tape at 100%, an aluminum braid at 60%, a second Duofoil tape at 100%, and an aluminum braid at 40%.

3131A and 3132A rows from the technical data sheets opened October 28, 2026.
Item3131A3132A
Impedance120 Ohm ± 3 Ohm100 Ohm ± 3 Ohm
JacketPVC, 0.301 inPVDF, 0.274 in
UL temperature75°C150°C
Operating range-30°C to +75°C-20°C to +150°C
ListingCL2R, CMRCMP
Cross-referencePlenum number 3132ANon-plenum number 3131A
Conductor DCR28 Ohm/1000ft28 Ohm/1000ft
Outer-shield DCR3.6 Ohm/1000ft7.2 Ohm/1000ft

120 Ohm and 100 Ohm, with the shield DCR from the sheet

As of October 28, 2026, both sheets list nominal conductor DCR of 28 Ohm/1000ft, nominal delay of 1.2 ns/ft, and velocity of 82%. Capacitance conductor to shield is 16.2 pF/ft on 3131A and 16.3 pF/ft on 3132A. Inductance is 0.097 µH/ft on 3131A and 0.093 µH/ft on 3132A. Outer-shield DCR and the outer-conductor DCR column are 3.6 Ohm/1000ft on 3131A and 7.2 Ohm/1000ft on 3132A. None of those DCR, capacitance, or inductance cells print a metric figure. Nominal insertion loss at 1 MHz is 0.35 dB/100ft on 3131A and 0.36 dB/100ft on 3132A. At 100 MHz it is 1.97 dB/100ft on 3131A and 2.12 dB/100ft on 3132A. Both tables continue through 400 MHz. The structural-return-loss table on each sheet prints 23 dB at 1 MHz, and the cells from 2 MHz through 400 MHz are empty. 3131A's notes also say SRL minimum 23 dB from 5 MHz to 50 MHz. 3132A's notes say the cable is sweep tested from 5 MHz to 400 MHz and do not repeat that 5 MHz to 50 MHz SRL span. Tilt on 3131A is 0.53 dB/100 M from 5 to 10 MHz and 0.89 dB/100 M from 10 to 20 MHz. Tilt on 3132A is .48 dB/100 M from 5 to 10 MHz and .93 dB/100 M from 10 to 20 MHz.

3131A's UL voltage rating, in the flammability block, is 300 V RMS, as of October 28, 2026. 3132A prints 300 V RMS in the voltage cell and again in the flammability block. NEC/(UL) compliance is CL2R, CMR on 3131A, and the NEC articles cell names Article 800. CEC compliance on 3131A is CMG. NEC/(UL) and CEC compliance on 3132A are CMP, and that sheet does not print Article 800 in the compliance cell. Flammability on 3131A is UL 1666 riser and CSA FT4. Flammability on 3132A is NFPA 262 and FT6. 3131A prints CPR Euroclass Eca and an IEEE cell of 802.4 MAP and 802.7 MIni-MAP, in that capitalization. 3132A does not print a CPR class or an IEEE cell. Suitability on 3132A is burial yes and outdoor yes. 3131A does not print those suitability cells.

Pull, bend, and the gray DEC reel

As of October 28, 2026, 3131A lists weight 33 lbs/1000ft, maximum recommended pulling tension 162 lbs, and minimum minor-axis bend radius 3 in. 3132A lists weight 43 lbs/1000ft, pulling tension 104 lbs, and bend radius 2.75 in. None of those cells print a kilogram or a millimeter. Both variant rows are gray DEC reels at 1,000 ft: 3131A F2V1000 and 3132A F2V1000. 3132A prints a footnote that defines C as a crate reel. The variant row on that sheet does not print the letter C. 3131A's variant row does not print a footnote letter. Page revision is 0.454 on 3131A and 0.418 on 3132A, both dated 02-20-2026. Both notes say tap marks every 2.6 meters. 3131A's note also says sweep tested from 5 to 400 MHz.

What to copy onto the cable line

  • Part: 3131A or 3132A, from the sheet opened October 28, 2026.
  • Impedance: 120 Ohm ± 3 Ohm, or 100 Ohm ± 3 Ohm.
  • Jacket: PVC at 0.301 in, or PVDF at 0.274 in.
  • Temperature: 75°C and -30°C to +75°C, or 150°C and -20°C to +150°C.
  • Listing: CL2R and CMR, or CMP.
  • Cross-reference: plenum number 3132A, or non-plenum number 3131A, copied with the Ohm cell of the sheet you named.

3131A or 3132A note

Name the coax and copy the impedance, jacket, and temperature line from that sheet.

This prepares a request. It does not send one.

Questions these sheets answer

Does the non-plenum number keep 100 Ohm?

3132A prints 100 Ohm ± 3 Ohm, as of October 28, 2026. Its non-plenum number is 3131A, and that sheet prints 120 Ohm ± 3 Ohm. Copy the Ohm cell from the part number on the request.

Does 0.274 in describe 3131A?

3132A's jacket cell is PVDF at 0.274 in, as of October 28, 2026. 3131A's jacket cell is PVC at 0.301 in. Neither cell prints a millimeter.

Which insulation name goes on 3131A?

The 3131A description says PO insulation, as of October 28, 2026. The insulation cell says polyethylene foam, gas injected, at 0.18 in. The request can carry both lines. 3132A's description and insulation cell both say FEP foam.

Sources

Impedance, jacket, temperature, listing, shield, and the cross-reference cells are from the Belden 3131A and 3132A technical data sheets. Both were opened October 28, 2026. 3132A's 100 Ohm cell matches the reading already on the 3093A comparison. The 120 Ohm cell is on 3131A.