Industrial networking
Belden 8777 at 50 Ohm or 3092A at 75 Ohm
Use 8777 for the Modbus 22 AWG 3-pair row. Use 3092A for the Modbus II 18 AWG quad-shield coax.
On this page
Use Belden 8777 when the line follows Belden's Modbus category row for a 22 AWG, 3-pair standard modem drop. As of October 25, 2026, the 8777 page lists three 22 AWG (7x30) tinned-copper pairs, a PVC jacket with a nominal diameter of 0.273 in (6.93 mm), and a nominal characteristic impedance of 50 Ohm. Use Belden 3092A when the line follows the Modbus II row for an 18 AWG quad-shield coax. As of the same day, that page lists one 18 AWG solid bare-copper-covered-steel conductor, a PVC jacket with a nominal diameter of 0.303 in (7.70 mm), and a nominal characteristic impedance of 75 Ohm. A 120 Ohm RS-485 pair is Belden 9841, on the 120 Ohm and 150 Ohm page.
The category table assigns the two part numbers
Belden's Modbus category page, opened October 25, 2026, prints a Modbus row at 22 AWG, 3 pair, described as standard modem drop cable, and the product link is 8777. The Modbus II row is 18 AWG, 1 coax, described as standard quad shield coax, and the product link is 3092A. The same table's Modbus Plus row is 24 AWG, 1 pair, described as RS485 paired cable, with a PDF link and no product number in the cell. A request that starts from this table copies the row name, then opens the product page that row links.
The 8777 title, as of October 25, 2026, is Audio, Control & Instrument, #22-3pr, PP, individual foil, PVC jacket, CM. The suitable-applications cell names low-voltage analog signals, low-voltage digital control, line-level audio, computer communication, and panel wiring. The word Modbus is on the category row. It is not in the 8777 title. 3092A's suitable-applications cell names harsh environment, factory automation, ControlNet, Modbus II, and industrial coax. Copy Modbus II onto 3092A from that cell. Copy the 3-pair drop onto 8777 from the category row.
Three shielded pairs, or one quad-shield coax
As of October 25, 2026, 8777 insulation is polypropylene, 0.011 in (0.28 mm) thick, with a nominal insulation diameter of 0.050 in (1.3 mm). Pair colors are black and red, black and white, and black and green. Each pair has a bi-laminate aluminum-and-polyester tape at 100% coverage and a 22 AWG (7x30) tinned-copper drain. The PVC jacket is 0.034 in (0.86 mm) thick. Overall cable diameter is 0.273 in (6.93 mm). The part-number table lists Chrome put-ups.
As of October 25, 2026, 3092A is RG-6. The conductor nominal diameter is 0.040 in. Insulation is foam polyethylene, white, with a nominal insulation diameter of 0.180 in (4.57 mm). The outer shield is four layers: a Duobond II tri-laminate tape at 100%, an aluminum braid at 60%, a Duofoil tri-laminate tape at 100%, and an aluminum braid at 40%. The PVC jacket nominal diameter is 0.303 in (7.70 mm). Part-number rows list black and blue X7E put-ups. The plenum-number cell on this page is 3093A. High-flex and armor rows are separate parts, on the 3092F page and the 123092A page.
| Item | 8777 | 3092A |
|---|---|---|
| Category row | Modbus, 22 AWG, 3 pair | Modbus II, 18 AWG, 1 coax |
| Conductor | 22 AWG, 7x30, tinned copper, 3 pairs | 18 AWG, solid, bare copper covered steel |
| Shield | Foil and drain on each pair | Tape, 60% braid, tape, 40% braid |
| Nominal jacket OD | 0.273 in (6.93 mm) | 0.303 in (7.70 mm) |
| Impedance | 50 Ohm | 75 Ohm |
| Maximum current | 2.8 A per conductor at 25°C | No current cell on the electrical table |
| UL voltage | 300 V (CM), 30 V (UL AWM 2919) | 300 V (CMR, CMG) |
| Operating temperature | -20°C to +80°C | -30°C to +75°C |
50 Ohm and 75 Ohm stay on their own pages
As of October 25, 2026, 8777 lists nominal conductor DCR of 18.2 Ohm/1000ft, inner-shield DCR of 12.39 Ohm/1000ft (40.65 Ohm/km), capacitance of 30 pF/ft (98 pF/m) conductor to conductor and 55 pF/ft (180 pF/m) conductor to other, inductance of 0.18 µH/ft (0.59 µH/m), and velocity of 66%. Maximum current is 2.8 A per conductor at 25°C. UL voltage is 300 V (CM) and 30 V (UL AWM 2919). AWM compliance is AWM 2919.
As of October 25, 2026, 3092A lists conductor DCR of 28 Ohm/1000ft, outer-shield DCR of 2.6 Ohm/1000ft (8.5 Ohm/km), capacitance of 16.2 pF/ft (53.1 pF/m) conductor to shield, and velocity of 83%. Minimum structural return loss is 23 dB from 5 MHz to 50 MHz. Nominal attenuation is 0.35 dB/100ft at 1 MHz, 0.59 dB/100ft at 10 MHz, and 1.97 dB/100ft at 100 MHz. The same table continues at 2, 5, 20, 50, 200, 300, and 400 MHz. There is no ampacity cell beside the impedance. A 2.8 A figure belongs on 8777.
Listing, temperature, and bend
As of October 25, 2026, 8777 lists UL temperature 80°C, operating temperature -20°C to +80°C, and storage -40°C to +80°C. Minimum bend radius is 2.7 in (69 mm) for stationary use and for installation. Maximum pull tension is 63.7 lbs (28.9 kg). Bulk cable weight is 39 lbs/1000ft. Environmental suitability is indoor. Flammability is UL 1685 FT4 Loading and IEC 60332-1-2. CPR is Euroclass Eca and UKCA Class Eca. NEC compliance is Article 800, CM. The plenum-number cell names 88777, 87777, and 82777. The FEP plenum cable opened for this comparison is 88777, on the 8777 and 88777 page. 87777 and 82777 are on the 87777 and 82777 page. Page revision is 0.540, dated 02-20-2026.
As of October 25, 2026, 3092A lists UL temperature 75°C and operating temperature -30°C to +75°C. The bend table prints an installation minimum of 3 in (76 mm) and no stationary cell. Maximum pull tension is 162 lbs (73.5 kg). Bulk cable weight is 33 lbs/1000ft. Environmental suitability is indoor/outdoor, indoor, outdoor, sunlight resistance, and aerial when supported by messenger wire. Flammability is UL 1666 vertical shaft. CPR is Euroclass Eca. NEC compliance is CMR, CL2R, and CMG. Page revision is 0.602, dated 02-20-2026.
What to copy onto the cable line
- Row: Modbus 22 AWG 3-pair drop, or Modbus II 18 AWG coax, from the category page opened October 25, 2026.
- Part: 8777 or 3092A.
- Impedance: 50 Ohm on 8777, or 75 Ohm on 3092A.
- Shield: a foil and drain on each 8777 pair, or the four-layer quad shield on 3092A.
- Jacket diameter: 0.273 in (6.93 mm), or 0.303 in (7.70 mm).
- Voltage and operating temperature from that part's own table.
Questions these pages answer
Does the Modbus row use the 120 Ohm RS-485 cable?
The Modbus category page opened October 25, 2026 links 8777 for the 22 AWG 3-pair row. 8777's impedance cell is 50 Ohm. 9841, at 120 Ohm, is a different product page, and the category table does not list it. A request for the category's modem-drop row copies 50 Ohm.
Can the 0.303 in jacket be copied onto 8777?
0.303 in (7.70 mm) is the 3092A jacket diameter, as of October 25, 2026. 8777's jacket diameter is 0.273 in (6.93 mm). The pair count and the shield construction differ with the diameter.
Which number is the plenum cable?
The plenum-number cell on 3092A is 3093A. The high-temp link on the category page, under Modbus II, is 3132A, and that page prints 100 Ohm. Those two high-temp parts are on the 3093A and 3132A page.
Sources
Pair count, 50 Ohm, jacket diameter, voltage, and the plenum-number list are from the Belden 8777 page. Conductor, quad shield, 75 Ohm, and jacket diameter are from the Belden 3092A page. The row names and the product links are from the Belden Modbus category page. All three were opened October 25, 2026.