Industrial networking
Belden 8777 PVC or 88777 FEP Plenum
Use 8777 for the PVC CM cable at -20°C to +80°C. Use 88777 for the FEP CMP cable at -70°C to +200°C.
On this page
Use Belden 8777 when the 22 AWG 3-pair cable is PVC, listed CM, with an operating range of -20°C to +80°C. As of October 25, 2026, that page lists a nominal jacket diameter of 0.273 in (6.93 mm) and 50 Ohm, and its plenum-number cell includes 88777. Use Belden 88777 when the cable is FEP, listed CMP, with an operating range of -70°C to +200°C. As of the same day, that page lists a nominal jacket diameter of 0.236 in (5.99 mm), 50 Ohm, and 8777 as the non-plenum number. The Modbus category page links 88777 from the high-temp/plenum line under the 22 AWG 3-pair Modbus row. The coax choice is on the 8777 and 3092A page.
Same pair count, different insulation and drain
As of October 25, 2026, both pages list three pairs of 22 AWG, 7x30, tinned copper. Colors on both pages are black and red, black and white, and black and green. 8777 insulation is polypropylene, 0.011 in (0.28 mm), nominal insulation diameter 0.050 in (1.3 mm). 88777 insulation is FEP, 0.010 in (0.25 mm), nominal insulation diameter 0.049 in (1.2 mm). Each pair on both pages has a bi-laminate tape at 100% coverage. The 8777 drain is 22 AWG (7x30) tinned copper. The 88777 drain is 22 AWG (19x34) tinned copper. The jacket on 8777 is PVC, 0.034 in (0.86 mm), nominal diameter 0.273 in (6.93 mm). The jacket on 88777 is FEP, 0.015 in (0.38 mm), nominal diameter 0.236 in (5.99 mm).
The 8777 title is Audio, Control & Instrument, with a PVC jacket and CM. The 88777 title is the same family name, with an FEP jacket and CMP. 88777's suitable-applications cell adds extreme high and low temperature, chemical resistance, and outdoor and burial, and it still names the low-voltage analog, digital-control, audio, and panel-wiring uses. 8777's applications cell does not name outdoor or burial. Part-number rows list Chrome put-ups for 8777 and red put-ups for 88777, as of October 25, 2026.
| Item | 8777 | 88777 |
|---|---|---|
| Jacket | PVC, 0.034 in (0.86 mm) | FEP, 0.015 in (0.38 mm) |
| Nominal OD | 0.273 in (6.93 mm) | 0.236 in (5.99 mm) |
| Drain | 22 AWG, 7x30, tinned copper | 22 AWG, 19x34, tinned copper |
| Impedance | 50 Ohm | 50 Ohm |
| Listing | CM, Article 800 | CMP, Article 800 |
| UL temperature | 80°C | 150°C |
| Operating range | -20°C to +80°C | -70°C to +200°C |
| Cross-reference | Plenum numbers include 88777 | Non-plenum number 8777 |
50 Ohm on both, with a different voltage line
As of October 25, 2026, both pages list nominal conductor DCR of 18.2 Ohm/1000ft, inductance of 0.18 µH/ft (0.59 µH/m), and maximum current of 2.8 A per conductor at 25°C. 8777 inner-shield DCR is 12.39 Ohm/1000ft (40.65 Ohm/km). 88777 inner-shield DCR is 11.54 Ohm/1000ft (37.86 Ohm/km). Conductor-to-conductor capacitance is 30 pF/ft (98 pF/m) on 8777 and 31 pF/ft (100 pF/m) on 88777. Conductor-to-other capacitance is 55 pF/ft (180 pF/m) on 8777 and 67 pF/ft (220 pF/m) on 88777. Velocity is 66% on 8777 and 69% on 88777.
8777's voltage cell is 300 V (CM) and 30 V (UL AWM 2919), and the AWM compliance line is AWM 2919. 88777's voltage cell is 300 V (CMG). The 88777 page opened October 25, 2026 does not print an AWM style number. 88777 also prints a maximum conductor DCR of 160 Ohm/km beside the nominal 18.2 Ohm/1000ft. The two cells use different units. Copy both, each with the unit printed on that cell. The 30 V AWM line stays on 8777.
Where the listing and the temperature cell differ
As of October 25, 2026, 8777 environmental suitability is indoor. Flammability is UL 1685 FT4 Loading and IEC 60332-1-2. Minimum bend radius is 2.7 in (69 mm) stationary and installation. Maximum pull tension is 63.7 lbs (28.9 kg). Weight is 39 lbs/1000ft. Storage is -40°C to +80°C. The plenum-number cell names 88777, 87777, and 82777. The 8777 technical data sheet opened October 27, 2026 still prints that cell. Jacket, impedance, and current for 87777 and 82777 are on the 87777 and 82777 page. Page revision is 0.540, dated 02-20-2026.
As of October 25, 2026, 88777 environmental suitability is indoor, sunlight resistance, UV resistance, and oil resistance. Flammability is NFPA 262 (UL 910), FT6, and IEC 60332-1-2. NEC compliance is Article 800, CMP. CEC compliance is CMP. Minimum bend radius is 2.3 in (58 mm) stationary and installation. Maximum pull tension is 64.1 lbs (29.1 kg). Weight is 37 lbs/1000ft. The notes say Teflon is a registered trademark used under license. Page revision is 0.550, dated 09-07-2025. The category page's high-temp/plenum link under the 3-pair Modbus row is this part number.
What to copy onto the cable line
- Part: 8777 or 88777, from the page opened October 25, 2026.
- Jacket: PVC and CM, or FEP and CMP.
- Operating range: -20°C to +80°C, or -70°C to +200°C.
- Nominal diameter: 0.273 in (6.93 mm), or 0.236 in (5.99 mm).
- Impedance: 50 Ohm on the part you named.
- Drain stranding: 7x30 on 8777, or 19x34 on 88777.
Questions these two pages answer
Does 50 Ohm pick the plenum cable?
Both impedance cells are 50 Ohm, as of October 25, 2026. The jacket material, the CMP or CM listing, and the operating range pick 88777 or 8777. A request that says only 50 Ohm and 22 AWG has not chosen the jacket.
Where is the 30 V AWM line?
30 V (UL AWM 2919) is on 8777, as of October 25, 2026. 88777's voltage cell is 300 V (CMG). The AWM style stays with the part that prints it.
Is 88777 the plenum version of 3092A?
88777's non-plenum number is 8777. 3092A's plenum number is 3093A. The 100 Ohm high-temp coax linked from the category page is 3132A, on the 3093A and 3132A page.
Sources
Jacket, diameter, drain, voltage, temperature, and the plenum-number list are from the Belden 8777 and 88777 pages. The high-temp link under the 3-pair Modbus row is from the Belden Modbus category page. All three were opened October 25, 2026. 87777 and 82777 were opened October 27, 2026 for the page linked above.