Use 9841 for the non-plenum CM sheet at 0.232 in and 2.1 A. Use 82841 for the plenum CMP sheet at 0.204 in and 4 A. Both list 120 Ohm.
On this page
Use Belden 9841 when the one-pair RS-485 cable is the non-plenum CM number. As of October 29, 2026, that sheet lists a PVC jacket of 0.232 in (5.89 mm), polyethylene insulation, 2.1 A per conductor at 25°C with a 10°C rise note, and an operating range of -30°C to +80°C. Use Belden 82841 when the one-pair cable is the plenum CMP number. As of the same day, that sheet lists a PVC jacket of 0.204 in (5.18 mm), FEP foam insulation, 4 A per conductor at 25°C, and an operating range of 0°C to +75°C. Both sheets list one 24 AWG pair and 120 Ohm. 9841's plenum-number cell names 82841 and 89841. 82841's non-plenum-number cell names 9841 and 9841ZH. The two-pair plenum number is 82842, on the 9842 and 82842 page.
The sheets name each other, and the line card puts both on the light-industrial row
As of October 29, 2026, 9841 prints Plenum (the cell is labeled Plenum Number) as 82841, 89841, and Non-Plenum Number as 9841ZH. 82841 prints Non-Plenum Number as 9841, 9841ZH, and does not print a plenum-number cell of its own. The April 2022 RS-485 line card lists both as one pair, 24 AWG, PVC, SF/UTP, light industrial environment. That card's rating cell is CMG for 9841 and CMP for 82841. The technical data sheet for 9841 prints CM, not CMG. Copy CM from the 9841 sheet and CMP from the 82841 sheet. The line card's CMG cell stays a line-card reading. 89841 is the line card's FEP jacket row at CMP. The 89841 sheet, opened November 5, 2026, lists that FEP jacket at 0.204 in (5.18 mm), the same diameter 82841 prints for PVC, with UL temperature 200°C. The jacket choice is on the 82841 and 89841 page.
24 AWG 7x32, polyethylene at 0.232 in or FEP foam at 0.204 in
As of October 29, 2026, both sheets list one pair of 24 AWG 7x32 tinned copper, a 100% bi-laminate tape with a 24 AWG (7x32) tinned-copper drain, and a 90% tinned-copper braid. Pair colors on both are white/blue stripe and blue/white stripe. 9841's insulation is polyethylene, 0.023 in (0.58 mm) thick, nominal insulation diameter 0.068 in (1.7 mm). The jacket is PVC, 0.035 in (0.89 mm) thick, nominal diameter 0.232 in (5.89 mm), and the jacket OD note is plus or minus 0.020 in. 82841's insulation is FEP foam, 0.025 in (0.64 mm) thick, nominal insulation diameter 0.074 in (1.9 mm). The jacket is PVC, 0.015 in (0.38 mm) thick, nominal diameter 0.204 in (5.18 mm). That sheet does not print a jacket OD tolerance. Suitable applications on both name RS-485, POS, computer communications, low voltage analog signals, low voltage digital control, line level audio, panel wiring, and serial communication for PLCs, VFDs, HMIs, motors, RTU, and SCADA.
| Item | 9841 | 82841 |
|---|---|---|
| Listing on the sheet | CM | CMP |
| Jacket | PVC, 0.232 in | PVC, 0.204 in |
| Insulation | Polyethylene | FEP foam |
| Impedance | 120 Ohm | 120 Ohm |
| Current | 2.1 A at 25°C, 10°C rise note | 4 A at 25°C |
| Operating range | -30°C to +80°C | 0°C to +75°C |
| UL temperature | 80°C | 75°C |
| Cross-reference | Plenum number 82841, 89841 | Non-plenum number 9841, 9841ZH |
120 Ohm on both, with a different velocity and a different current note
As of October 29, 2026, both impedance cells print 120 Ohm. 9841 lists nominal conductor DCR of 24 Ohm/1000ft (79 Ohm/km), capacitance conductor to conductor of 12.8 pF/ft (42.0 pF/m), capacitance to the other conductors plus shield of 23 pF/ft (75 pF/m), delay of 1.6 ns/ft, and velocity of 66%. Outer-shield DCR is 3.4 Ohm/1000ft (11 Ohm/km). The current cell is 2.1 A per conductor at 25°C, and the same cell names a 10°C temperature rise. 82841 lists nominal conductor DCR of 24 Ohm/1000ft, with no kilometer figure in that cell, capacitance of 12 pF/ft (39 pF/m) and 22 pF/ft (72 pF/m), and velocity of 76%. The 82841 row does not print a delay. Outer-shield DCR is 3.1 Ohm/1000ft (10 Ohm/km). The current cell is 4 A per conductor at 25°C, and it does not print the 10°C rise note. Nominal insertion loss at 1 MHz is 0.6 dB/100ft on both sheets. Neither high-frequency table prints a row past 1 MHz.
9841's UL voltage rating, as of October 29, 2026, is 300 V (CM) and 30 V (UL AWM 2919). NEC / UL compliance is Article 800, CM. AWM compliance is AWM 2919. CEC / C(UL) compliance is CM. The other-standard cell names DMX-512. Flammability is UL 1685 UL Loading and IEC 60332-1-2. CPR is Euroclass Eca and UKCA Class Eca. 82841's UL voltage rating is 300 V (CMP). NEC / UL compliance is Article 800, CMP. CEC / C(UL) compliance is CMP. That sheet does not print an AWM line or a DMX-512 line. Flammability is NFPA 262, UL 910 (Plenum), FT6, and IEC 60332-1-2. CPR is Euroclass Eca, and the cell does not print a UKCA class. Environmental suitability on both sheets is indoor.
Pull, bend, and the natural plenum put-ups
As of October 29, 2026, 9841 lists UL temperature 80°C, operating temperature -30°C to +80°C, minimum bend radius 2.5 in (64 mm) for stationary and installation, maximum pull tension 72.3 lbs (32.8 kg), and bulk weight 36 lbs/1000ft (54 kg/km). 82841 lists UL temperature 75°C, operating temperature 0°C to +75°C, bend radius 2.25 in (57.2 mm) for stationary and installation, pull tension 45.7 lbs (20.7 kg), and bulk weight 26 lbs/1000ft. The weight cell does not print a kilogram figure. Page revision is 0.725, dated 02-25-2026, on 9841, and 0.549, dated 02-20-2026, on 82841. The 82841 variant table prints 82841 8771000, 82841 877500, and 82841 8775000, all natural, and does not print a length in that table. Footnote C, crate reel put-up, is on 8771000.
What to copy onto the cable line
- Part: 9841 or 82841, from the sheet opened October 29, 2026.
- Listing: CM, or CMP. Leave the line card's CMG cell off the 9841 line.
- Jacket: PVC at 0.232 in with the 0.020 in tolerance, or PVC at 0.204 in with no tolerance printed.
- Insulation: polyethylene, or FEP foam.
- Impedance: 120 Ohm on either part.
- Current: 2.1 A at 25°C with the 10°C rise note, or 4 A at 25°C.
- Temperature: 80°C and -30°C to +80°C, or 75°C and 0°C to +75°C.
- Cross-reference: plenum numbers 82841 and 89841, or non-plenum numbers 9841 and 9841ZH. 89841's FEP jacket is on the plenum-jacket page.
Questions these sheets answer
Does CMP change the 120 Ohm cell?
Both sheets print 120 Ohm, as of October 29, 2026. CMP on 82841 changes the listing, the insulation, the jacket diameter, the current, and the operating low. It does not change the Ohm cell.
Does 82841 keep -30°C?
9841's operating range is -30°C to +80°C, as of October 29, 2026. 82841's operating range is 0°C to +75°C. The plenum sheet does not print -30°C.
Is 89841 the same cable as 82841?
9841's plenum-number cell names 82841 and 89841, as of October 29, 2026. The line card lists 82841 as PVC and 89841 as FEP, both CMP. The 89841 sheet, opened November 5, 2026, lists an FEP jacket, UL temperature 200°C, and an operating range of -70°C to +200°C. 82841's jacket cell remains PVC, UL temperature 75°C, and an operating range of 0°C to +75°C. Both plenum sheets print 0.204 in and 4 A at 25°C.
Sources
Pair count, jacket, insulation, impedance, current, temperature, listing, and the cross-reference cells for 9841 and 82841 are from those technical data sheets, opened October 29, 2026. The April 2022 RS-485 line card, opened the same day, is the source for the CMG cell on 9841. The 89841 jacket, 200°C, and -70°C to +200°C are from the 89841 technical data sheet opened November 5, 2026.