Skip to the guide

Power connections

Busbar Insulation Shroud or Heat-Shrink Tubing

Use a Galathermo PVC shroud on a joint, at the thickness for that voltage. Use Storm's heat-shrink row when the cover is tubing on the bar.

Rust Belt Industrials · November 7, 2026 · 6 min read

On this page

Use a Galathermo PVC shroud when the cover is a removable boot on a busbar joint, tee, or elbow. As of November 7, 2026, its thickness table lists 1.25 mm at 3.3 kV, 2.00 mm at 12.0 kV, 2.50 mm at 18.0 kV, 3.00 mm at 24.0 kV, and 4.50 mm at 38.0 kV, and the continuous operating temperature is -20°C to 115°C. Use a heat-shrink tube when the cover is tubing on a rectangular, square, or round bar. As of the same day, Storm's heat-shrink table lists Raychem BBIT at 35/36 kV with thermal endurance 105°C, Raychem BPTM at 25 kV and 125°C, and 3M FP-301 at 600 V and -55°C to 135°C. The full heat-shrink rows are on the heat-shrink page.

The shroud is a PVC boot with a thickness for each voltage

The Galathermo sheet opened November 7, 2026, issue 2 dated February 2026, calls the part a bus bar insulating shroud or boot. It says the vinyl boot is a flexible cover for busbar and switchgear connections, that it can be installed, removed, or replaced, and that it is made from PVC. It says the boot suits joint work, including tees and elbows, and that it is for outdoor or indoor use with resistance to UV and ozone. The standards line says the part is tested to ANSI C37.20.2 for medium-voltage switchgear application up to 36 kV. The thickness table's highest row is 38.0 kV at 4.50 mm. Those two voltage figures are both on the sheet. Copy the standards line when the request cites ANSI C37.20.2 up to 36 kV. Copy the thickness row when the request cites a voltage in the table, including the 38.0 kV row.

As of November 7, 2026, the thickness rows are 3.3 kV at 1.25 mm, 12.0 kV at 2.00 mm, 18.0 kV at 2.50 mm, 24.0 kV at 3.00 mm, and 38.0 kV at 4.50 mm. A 12 kV joint uses the 2.00 mm row. A 24 kV joint uses the 3.00 mm row. The sheet does not print a bar width or a catalog code next to those rows. It says new molds can be developed and that the shape can be customized. The overlapping design is described as additional protection against flashover. Fasteners are included. No fastener size is printed.

Galathermo shroud thickness rows and the material table, issue 2, opened November 7, 2026.
Line on the sheetFigureTest or note
3.3 kV thickness1.25 mmRecommended thickness table
12.0 kV thickness2.00 mmRecommended thickness table
18.0 kV thickness2.50 mmRecommended thickness table
24.0 kV thickness3.00 mmRecommended thickness table
38.0 kV thickness4.50 mmRecommended thickness table
Standards lineUp to 36 kVANSI C37.20.2
Dielectric strength16 kV/mm minimumASTM D149
Continuous operating temperature-20°C to 115°CIEC 216
Tensile strength12 N/mm² minimumASTM D638
Elongation350 percent minimumASTM D638
Hardness65 ± 5 Shore AASTM D2240
FlammabilityPassUL 94 V-0

The material table is separate from the voltage thickness

As of November 7, 2026, the technical specification lists dielectric strength of 16 kV/mm minimum to ASTM D149, tensile strength of 12 N/mm² minimum to ASTM D638, elongation of 350 percent minimum to ASTM D638, density of 1.23 g/cm³ to ASTM D792, water absorption of 0.5 percent maximum to ASTM D570, hardness of 65 ± 5 Shore A to ASTM D2240, continuous operating temperature of -20°C to 115°C to IEC 216, and flammability pass to UL 94 V-0. The qualification report named on the sheet is QR 1018. Density and tensile strength are material cells. They are not the thickness that goes with 12 kV or 24 kV. A joint at 115°C is at the top of the continuous-temperature cell. The sheet does not print a short-time temperature above 115°C.

Heat-shrink tubing is the cover on the bar, from Storm's table

Storm's heat-shrink page, opened November 7, 2026, describes tubing that covers and insulates rectangular, square, or round bus bars. It is not a boot for a tee or an elbow. The thermal cells on that table are not the shroud's -20°C to 115°C line. BBIT on Storm's table is 35/36 kV at 105°C. BPTM is 25 kV at 125°C. FP-301 and RNF-100 are 600 V at -55°C to 135°C. LVIT is 1 kV at 105°C. NU-Sleeve SG-200 is 7 kV at -55°C to 200°C. BBI-A lists 5, 8, 15, 25, and 35 kV at 110°C. A bar run that needs a sleeve copies one of those rows. A joint that needs a removable PVC boot copies a Galathermo thickness row. The two can both appear on one drawing, on different lines.

The shroud sheet's 36 kV standards line and Storm's BBIT 35/36 kV cell are close titles for different parts, as of November 7, 2026. The shroud is the PVC boot, with a thickness from 1.25 mm to 4.50 mm and a continuous temperature of -20°C to 115°C. BBIT on Storm's table is red heat-shrink tubing at thermal endurance 105°C, with flammability ANSI C37.20 and IEEE-27. The shroud's flammability cell is UL 94 V-0 pass. Epoxy powder on the bar, applied after fabrication, remains the method on the epoxy and BBIT page. This page does not move the shroud thickness onto that powder.

What to copy onto the cover line

  • Cover: Galathermo PVC shroud, or a heat-shrink product from Storm's table, as opened November 7, 2026.
  • Shroud voltage and thickness: 3.3 kV at 1.25 mm, 12.0 kV at 2.00 mm, 18.0 kV at 2.50 mm, 24.0 kV at 3.00 mm, or 38.0 kV at 4.50 mm.
  • Standards line, when the request cites it: ANSI C37.20.2 up to 36 kV. That line is separate from the 38.0 kV thickness row.
  • Shroud temperature: -20°C to 115°C. Dielectric strength: 16 kV/mm minimum.
  • Heat-shrink product, voltage class, and thermal endurance from the heat-shrink page, when the cover is tubing on the bar.
  • Joint shape: tee, elbow, or the shape the sheet says can be molded. No catalog code is printed next to the thickness rows.

Busbar shroud or heat-shrink note

Name the cover. A shroud uses a thickness row. Tubing uses a heat-shrink product.

This prepares a request. It does not send one.

Questions these cover pages answer

Does the 36 kV line set the 4.50 mm thickness?

The standards line says up to 36 kV to ANSI C37.20.2, as of November 7, 2026. The thickness table's top row is 38.0 kV at 4.50 mm. Copy the line the drawing cites. The sheet prints both.

Can the shroud use the heat-shrink 200°C cell?

The shroud's continuous operating temperature is -20°C to 115°C, as of November 7, 2026. The -55°C to 200°C cell belongs to Delfingen NU-Sleeve SG-200 on Storm's heat-shrink table, at 7 kV. That cell stays on the tubing row.

Where does the sheet say the boot goes?

The sheet says the boot is for busbar joint work, including tees and elbows, and that it can be removed, as of November 7, 2026. Storm's heat-shrink page describes tubing on rectangular, square, or round bars.

Sources

Shroud thickness, the 36 kV standards line, and the material table are from Galathermo's bus bar insulating shroud sheet, issue 2, February 2026. Heat-shrink voltage and thermal endurance are from Storm's heat-shrink table. Both were opened November 7, 2026.