Siemens 6XV1840-2AH10 Type A or 6XV1840-3AH10 Type C
Use 6XV1840-2AH10 for Type A rigid cores, PVC, and 100 m at 100BaseTX. Use 6XV1840-3AH10 for Type C cable-carrier motion, PUR, and 85 m at 100BaseTX.
On this page
Use Siemens 6XV1840-2AH10 when the PROFINET cable is Type A with rigid cores for fast installation. As of October 27, 2026, that page lists a PVC sheath of 6.5 mm with a symmetrical tolerance of 0.2 mm, impedance of 100 Ohm with a 15% relative symmetrical tolerance from 1 MHz to 100 MHz, and 100 m for 100BaseTX. Use Siemens 6XV1840-3AH10 when the cable is Type C for continuous motion in a cable carrier. As of the same day, that page lists a PUR sheath of 6.5 mm with the same 0.2 mm tolerance, impedance of 100 Ohm with a 5% relative symmetrical tolerance, 4 million bending cycles, and 85 m for 100BaseTX. Both are IE FC TP 2x2 cables, 4-core, shielded, Cat5e, sold by the meter, with a minimum order quantity of 20 m. LAPP's Type A and Type C examples are a different pair of articles, on the PROFINET type page.
Type A is the rigid installation article, Type C is the carrier article
The 2AH10 product type, as of October 27, 2026, is IE FC TP Standard Cable GP 2x2 (Type A). Suitability is a standard cable with rigid cores for fast installation. The description says it is a TP installation cable for connection to IE FC RJ45 2x2, for universal use, 4-core, shielded CAT 5E. Maximum delivery unit is 4,000 m. The mall page prints last modified 3/10/2026 and Date 10/15/2026. The 3AH10 product type is IE FC TP Trailing Cable 2x2 (Type C). Suitability is continuous motion control in a cable carrier. The description says it is for connection to an FC outlet RJ45, for cable carrier applications, and it names 4 million bending cycles. Maximum delivery unit is 2,000 m. That page prints last modified 3/10/2026 and Date 10/14/2026. Both brand lines say SIMATIC NET. Both say FastConnect yes.
Same 6.5 mm sheath diameter, PVC or PUR
As of October 27, 2026, both pages list 4 electrical cores, a shield described as SF/UTP, overlapped aluminum-clad foil, sheathed in a protective braided shield of tinned copper wires, wire insulation of polyethylene, insulation color white/yellow/blue/orange, and a green cable sheath. Sheath outer diameter is 6.5 mm on both, with a symmetrical tolerance of 0.2 mm. Wire insulation diameter is 1.5 mm on both. Inner sheath diameter is 3.9 mm on both. 2AH10's inner sheath material is PVC and the cable sheath material is PVC. The inner conductor diameter is 0.64 mm, and the AWG22 insulated-conductor cell is 0.64 mm. The cable designation is SF/UTP, 2YY (ST) CY 2x2x0,64/1,5-100 GN. 3AH10's inner sheath material is FRNC and the cable sheath material is PUR (TPE-U). The inner conductor diameter is 0.75 mm, and the AWG22 insulated-conductor cell is 0.75 mm. The cable designation is SF/UTP, 2YH (ST) C11Y 2x2x0,75/1,5-100 LI GN VZN FRNC.
| Item | 6XV1840-2AH10 | 6XV1840-3AH10 |
|---|---|---|
| Type on the page | Type A, rigid cores | Type C, cable carrier |
| Sheath | PVC, 6.5 mm | PUR (TPE-U), 6.5 mm |
| Sheath tolerance | 0.2 mm | 0.2 mm |
| Inner conductor | 0.64 mm | 0.75 mm |
| Impedance tolerance | 15% | 5% |
| 100BaseTX length | 100 m | 85 m |
| Loop resistance maximum | 115 mΩ/m | 120 mΩ/m |
| Halogen-free | No | Yes |
100 Ohm on both, with a different tolerance and a different link length
As of October 27, 2026, both pages list impedance of 100 Ohm from 1 MHz to 100 MHz. The relative symmetrical tolerance is 15% on 2AH10 and 5% on 3AH10. Attenuation maximum is 0.052 dB/m at 10 MHz and 0.195 dB/m at 100 MHz on 2AH10. It is 0.06 dB/m at 10 MHz and 0.22 dB/m at 100 MHz on 3AH10. Near-end crosstalk per length is 0.5 dB/m from 1 MHz to 100 MHz on both. Transfer impedance per length at 10 MHz is 10 mΩ/m on both. Loop resistance maximum is 115 mΩ/m on 2AH10 and 120 mΩ/m on 3AH10. Operating voltage RMS is 80 V on both. NVP is 69% on both. Test voltage is 2000 V AC core to core and 2000 V AC core to shield on both. The note on both pages says electrical properties are measured at 20°C. 100BaseTX length is 100 m on 2AH10 and 85 m on 3AH10.
49 mm is the multiple-bend cell on both
As of October 27, 2026, both pages list a single-bend minimum of 19.5 mm and a multiple-bend minimum of 49 mm. 3AH10 adds a continuous-bending minimum of 100 mm. The bending-cycle cell is 4000000, and the same cell says the cable is drag chain suitable for 4 million bending cycles at a bending radius of 100 mm, a speed of 4 m/s, and an acceleration of 4 m/s². 2AH10 does not print a continuous-bending cell or a cycle count. Tensile load maximum is 150 N on both. Weight is 61 kg/km on 2AH10 and 63 kg/km on 3AH10. Copy the Type C suitability line, the 100 mm continuous-bending cell, and the cycle count when the cable is for a carrier. The 49 mm cell is on both pages.
Operating temperature is -40°C to +75°C on both, as of October 27, 2026. Storage and transport are -40°C to +75°C on 2AH10 and -50°C to +75°C on 3AH10. Installation is -40°C to +60°C on 2AH10 and -20°C to +60°C on 3AH10. Halogen-free is No on 2AH10 and Yes on 3AH10. PoE and PoE+ are Yes on both. Silicon-free is Yes on both. Fire behavior on 2AH10 is flame resistant according to IEC 60332-3-24 (Category C) and UL 1685 (CSA FT 4). Fire behavior on 3AH10 is flame resistant according to IEC 60332-1-2. Burning class according to EN 13501-6 is Eca on both. Oil resistance on 2AH10 cites IEC 60811-2-1 (4 h / 70°C). Oil resistance on 3AH10 cites IEC 60811-2-1 (7x24h/90°C). Grease and water are conditional resistance on 2AH10 and resistant on 3AH10. UV radiation is resistant on both.
CMG, PLTC, and ITC on 2AH10, CMX on 3AH10
The 300 V listing on 2AH10, as of October 27, 2026, reads Yes; c(ETL)us / CMG / (ETL)us PLTC/ ITC / Sun Res. The 600 V style line reads Yes; cRUus AWM 21694 AWM I A/B 60°C 600V FT2. The 300 V listing on 3AH10 reads Yes; cULus / CMX. The 600 V style line reads Yes; cRU AWM I A/B 80°C 600V. That line does not print style 21694. Both pages say Cat5e, EAC, CE, RoHS, and ANSI/ISA-71.04 G3. The industrial-communication block on 2AH10 prints PROFINET Yes. The same block on 3AH10 prints PROFIBUS Yes and PROFINET Yes. Marine classification lines on both pages print No for the societies listed there. A PROFIBUS DP cable at 150 Ohm is a different match, on the 3079A and Type A page.
What to copy onto the cable line
- Article: 6XV1840-2AH10 or 6XV1840-3AH10, from the mall page opened October 27, 2026.
- Type: Type A rigid cores, or Type C cable carrier, including 4 million cycles if the article is 3AH10.
- Sheath: PVC or PUR, 6.5 mm, symmetrical tolerance 0.2 mm, and the inner-conductor diameter 0.64 mm or 0.75 mm.
- Impedance: 100 Ohm, with 15% or 5% relative symmetrical tolerance.
- 100BaseTX: 100 m, or 85 m.
- Listing: CMG / PLTC / ITC / Sun Res and AWM 21694, or CMX and the 80°C AWM line.
- Order length: sold by the meter, minimum order quantity 20 m, maximum delivery unit 4,000 m or 2,000 m.
Questions these pages answer
Does 6.5 mm mean the sheaths match?
Both sheath diameters are 6.5 mm with a 0.2 mm symmetrical tolerance, as of October 27, 2026. Copy the sheath material, PVC or PUR, the inner conductor, 0.64 mm or 0.75 mm, and the type letter with that diameter. The continuous-bending cell is on 3AH10.
Does Type C keep the 100 m 100BaseTX cell?
2AH10 prints 100 m for 100BaseTX, as of October 27, 2026. 3AH10 prints 85 m. Both impedance cells are 100 Ohm. Copy the link length with the article.
Does 49 mm choose the carrier cable?
Both multiple-bend cells are 49 mm, as of October 27, 2026. The carrier choice is the Type C suitability line, the continuous-bending cell of 100 mm, and the 4 million cycle note. Those three are on 3AH10.
Sources
Type, sheath, impedance tolerance, 100BaseTX length, bend, listing, and the order-quantity lines are from the Siemens mall data pages for 6XV1840-2AH10 and 6XV1840-3AH10. 2AH10 was opened again October 28, 2026, and the cells on this page still match. The 2AH10 page date line is 10/15/2026. The 3AH10 page date line is 10/14/2026. Type B marine article 6XV1840-4AH10 is on the 2AH10 and 4AH10 page.