Industrial networking
Belden 3076F 18 AWG or 3077F 22 AWG for Fieldbus
Use 3076F for the Type A 18 AWG row at 0.280 in and 5.2 A. Use 3077F for the Type B 22 AWG row at 0.197 in and 2.5 A. Both sheets list 100 Ohm.
On this page
Use Belden 3076F when the fieldbus pair is 18 AWG on the 300 V Type A flexible row. As of November 5, 2026, that sheet lists a PVC jacket of 0.280 in (7.11 mm), 5.2 A per conductor at 25°C, 300 V (CM, PLTC-ER), and a note that an orange jacket is Fieldbus and an intrinsically safe blue jacket is PROFIBUS PA. The light blue put-up on that sheet is 3076F 0061000 at 1,000 ft. Use Belden 3077F when the fieldbus pair is 22 AWG on the 300 V Type B flexible row. As of the same day, that sheet lists a PVC jacket of 0.197 in (5.00 mm), 2.5 A per conductor with no temperature in that cell, and 300 V (CM, PLTC). Its variant table prints orange put-ups and does not print a light blue row. Both characteristic-impedance cells print 100 Ohm. The Foundation Fieldbus category, opened November 6, 2026, is the page that prints those Type A and Type B row labels. 3076F's own standards block prints ISA/SP-50 Type A. 3077F's standards block does not print Type B. A 150 Ohm PROFIBUS DP cable is a different match, on the 3079A and PA page.
One pair, polypropylene, and a different gauge
As of November 5, 2026, 3076F is one pair of 18 AWG 7x26 tinned copper. Insulation is polypropylene, 0.022 in (0.56 mm) thick, nominal insulation diameter 0.088 in (2.2 mm), colors blue and orange. The shield is a 100% bi-laminate tape with a 20 AWG (7x28) tinned-copper drain. The jacket is PVC, 0.050 in (1.3 mm) thick, nominal diameter 0.280 in (7.11 mm). The jacket OD note is plus or minus 0.010. 3077F is one pair of 22 AWG 7x30 tinned copper. Insulation is polypropylene, 0.015 in (0.38 mm) thick, colors blue and orange. The insulation-diameter cell is not in the construction block that was read. The drain is 22 AWG (7x30) tinned copper on a 100% bi-laminate tape. The jacket is PVC, 0.037 in (0.94 mm) thick, nominal diameter 0.197 in (5.00 mm). The sheet does not print a jacket OD tolerance. Neither sheet prints the other part number. Both application cells also name harsh environment, oil and gas sites, petrochemical, humidity, dust, oil, and long distance. 3076F adds exposure to rodent, crush, or cut-through force.
| Item | 3076F | 3077F |
|---|---|---|
| Gauge | 18 AWG 7x26 | 22 AWG 7x30 |
| Jacket | PVC, 0.280 in | PVC, 0.197 in |
| Impedance | 100 Ohm | 100 Ohm |
| Current | 5.2 A at 25°C | 2.5 A, no temperature in the cell |
| Conductor DCR | 7.2 Ohm/1000ft | 17.1 Ohm/1000ft |
| Voltage | 300 V (CM, PLTC-ER) | 300 V (CM, PLTC) |
| Operating low | -40°C | -30°C |
| Type A cell | ISA/SP-50 Type A | No Type A line in the block read |
100 Ohm on both, at 5.2 A or 2.5 A
As of November 5, 2026, 3076F lists conductor DCR of 7.2 Ohm/1000ft, with no kilometer figure in that cell. Capacitance conductor to shield is 45 pF/ft (150 pF/m). Maximum capacitance unbalance is 1.2 pF/ft. The characteristic-impedance cell prints 100 Ohm. Inductance is 0.19 µH/ft (0.62 µH/m). Velocity is 66%. Current is 5.2 A per conductor at 25°C. Outer-shield DCR is 8.5 Ohm/1000ft (28 Ohm/km). Insertion loss at 0.039 MHz is 0.08 dB/100ft. Voltage is 300 V (CM, PLTC-ER) and 150 V (ITC-ER). 3077F lists conductor DCR of 17.1 Ohm/1000ft (56.1 Ohm/km). Capacitance conductor to shield is 44 pF/ft (140 pF/m). Unbalance is 1.2 pF/ft. Impedance is 100 Ohm. Inductance is 0.2 µH/ft (0.66 µH/m). Velocity is 66%. Current is 2.5 A per conductor, and that cell does not print a temperature. Outer-shield DCR is 11.4 Ohm/1000ft (37.4 Ohm/km). Insertion loss at 0.039 MHz is 0.14 dB/100ft. Voltage is 300 V (CM, PLTC) and 150 V (ITC).
Type A, PLTC-ER, and burial are on 3076F
As of November 5, 2026, 3076F lists UL temperature 105°C and operating temperature -40°C to +105°C. Stationary bend radius is 6.5 in (170 mm). Installation bend radius is 2.80 in (71.1 mm). Pull tension is 60 lbs (27 kg). Bulk weight is 44 lbs/1000ft. Suitability lists indoor, outdoor, sunlight resistance, oil resistance twice, and burial. Flammability is UL 1685 UL Loading, FT4, IEEE 1202, and IEC 60332-1-2. NEC / UL compliance is Article 725, Article 727, Article 800, CMG, ITC, PLTC, TC. CEC compliance is CMG. ISO/IEC compliance is IEC 61158-2. The other-standard cell is ISA/SP-50 Type A. 3077F lists UL temperature 105°C and operating temperature -30°C to +105°C. The mechanical block that was read does not print a bend radius. Pull tension is 27 lbs (12 kg). Bulk weight is 18 lbs/1000ft (27 kg/km). Suitability is outdoor and sunlight resistance. Flammability is UL 1685 UL Loading and IEC 60332-1-2. NEC / UL compliance is Article 725, Article 727, Article 800, CM, ITC, PLTC. CEC compliance is CM. The standards block that was read does not print IEC 61158-2 or ISA/SP-50 Type A. The notes say a CPE and low-smoke jacket is optional and do not name a part number for it. Page revision is 0.536 on 3076F and 0.526 on 3077F, both dated 02-20-2026.
Light blue is a 3076F row
As of November 5, 2026, 3076F's notes say Fieldbus: orange jacket, and PROFIBUS PA: intrinsically safe blue jacket, and they repeat the jacket diameter tolerance of plus or minus 0.010. The light blue row is 3076F 0061000, reel, 1,000 ft, footnote C. Orange rows that print a length are 3076F 003250 at 250 ft, 3076F 003500 at 500 ft, 3076F 0031000 at 1,000 ft, 3076F 0032500 at 2,500 ft, and 3076F 0035000 at 5,000 ft. The table also lists 3076F 00310000 in orange. That row does not print a length in the text that was read, so this page does not assign one. 3077F's variant table lists 3077F 003500 orange at 500 ft and 3077F 0031000 orange at 1,000 ft. It does not print a light blue row, and it does not print the orange-versus-blue note.
What to copy onto the cable line
- Part: 3076F or 3077F, from the sheet opened November 5, 2026.
- Gauge: 18 AWG 7x26, or 22 AWG 7x30. Insulation colors blue and orange on both.
- Jacket: PVC at 0.280 in with plus or minus 0.010, or PVC at 0.197 in.
- Impedance: 100 Ohm. Current: 5.2 A at 25°C, or 2.5 A with no temperature in the cell.
- Voltage: 300 V (CM, PLTC-ER) and 150 V (ITC-ER), or 300 V (CM, PLTC) and 150 V (ITC).
- 3076F also names ISA/SP-50 Type A and IEC 61158-2. 3077F's read standards block does not.
- Put-up: 3076F 0061000 light blue at 1,000 ft for the PA note, or an orange 3076F row. 3077F's printed rows are orange.
- Operating low: -40°C on 3076F, or -30°C on 3077F. UL temperature is 105°C on both.
Questions these sheets answer
Which put-up is the light blue PA jacket?
3076F 0061000 is the light blue reel at 1,000 ft, as of November 5, 2026. The notes assign the intrinsically safe blue jacket to PROFIBUS PA and the orange jacket to Fieldbus. 3077F's variant table does not print a light blue row.
Does 3077F print ISA/SP-50 Type A?
3076F's other-standard cell is ISA/SP-50 Type A, as of November 5, 2026, and the ISO/IEC cell is IEC 61158-2. 3077F's standards block that was read does not print either line. Both impedance cells still print 100 Ohm. The category page opened November 6, 2026 places 3076F on the 300 V Type A flexible row and 3077F on the 300 V Type B flexible row. The flexible foil and braid Type A rows are on the 3076F and 1334A page. The 150 Ohm high-speed row is on the 3077F and 3078F page.
Does 3077F print PLTC-ER?
3076F's voltage cell is 300 V (CM, PLTC-ER) and 150 V (ITC-ER), as of November 5, 2026. 3077F's voltage cell is 300 V (CM, PLTC) and 150 V (ITC). The NEC line on 3077F lists PLTC and does not list PLTC-ER.
Sources
Gauge, jacket, current, the orange and blue note, and the put-up rows are from the Belden 3076F and 3077F technical data sheets. Both were opened November 5, 2026, and the same cells were still on those sheets on November 6, 2026. The Type A and Type B row labels are from the Belden Foundation Fieldbus category, opened November 6, 2026. Neither sheet names the other part number. The length cell on 3076F 00310000 was blank in the text that was read.