Industrial networking
PROFIBUS DP vs PA Cable: Belden 3079A or UNITRONIC BUS PA
Use Belden 3079A when the impedance cell is 150 Ohm for DP. Use UNITRONIC BUS PA when the impedance cell is 100 ± 20 Ohm and the bit rate is 31.25 kbit/s.
On this page
Use Belden 3079A when the run is PROFIBUS DP and the impedance cell has to be 150 Ohm. As of October 23, 2026, that page prints one solid 22 AWG pair, a nominal characteristic impedance of 150 Ohm, and an outer diameter of 0.315 in (8.00 mm). Use LAPP UNITRONIC BUS PA when the run is PROFIBUS PA at 31.25 kbit/s and the impedance cell has to be 100 ± 20 Ohm. Article 2170234, opened the same day, is 1 x 2 x 1.3 mm with an outer diameter of 8 mm. The PI interconnection guideline, Version 1.4, puts DP Type A surge impedance at 135 to 165 ohm from 3 to 20 MHz, and the PA reference cable at 100 Ω ± 20% at 31.25 kHz. Belden's 150 Ohm sits in the DP window. It is not the PA reference impedance.
Belden 3079A is the 150 Ohm DP construction
The 3079A page describes the cable as Profibus, 1 pair 22 AWG solid bare copper, foam polyethylene insulation, an overall foil plus a tinned-copper braid at 65 percent coverage, and a PVC jacket. Suitable applications on that page include harsh environment, outdoors, and data transmission such as Profibus DP or PA. The electrical table prints conductor DCR of 18.9 Ohm/1000 ft (62.0 Ohm/km), characteristic impedance of 150 Ohm, inductance of 0.282 µH/ft (0.925 µH/m), velocity of propagation 78 percent, and a maximum current of 2.3 A per conductor at 25°C. UL voltage is 300 V for CMG and PLTC, and 600 V for AWM 20201. Operating temperature is -30°C to +75°C, with a UL temperature of 75°C. Stationary minimum bend radius is 2.4 in (61 mm). Insulation color code is red and green.
Jacket color is a put-up, not a second impedance. As of October 23, 2026, violet reels are 3079A 0071000 at 1,000 ft, 3079A 0072000 at 2,000 ft, and 3079A 0075000 at 5,000 ft. Chrome reels are 3079A 0601000 at 1,000 ft and 3079A 0602000 at 2,000 ft. The note calls the cable a Siemens Sinec L2 cable and points CPE and LSZH versions at other part numbers, YR45047, 3079T, and YR44731. Those other part numbers were not opened. The 150 Ohm cell is the 3079A cell.
PI's DP Type A row, in Table 1-3 of the interconnection guideline, is surge impedance 135 to 165 ohm at 3 to 20 MHz, capacitance at or below 30 pF/m, loop resistance at or below 110 ohm/km, solid core AWG 22/1, and flexible core greater than 0.32 mm². Belden prints 22 AWG solid and 150 Ohm, which sits in that impedance window, and it prints 62.0 Ohm/km as conductor DCR. Conductor DCR and loop resistance are different labels. This page does not convert one into the other. A special cable may deviate, the guideline says, and the surge impedance still has to be retained.
UNITRONIC BUS PA is the 100 ± 20 Ohm construction
The LAPP page says transmission technology for PROFIBUS-PA follows IEC 61158-2, and that the bit rate is 31.25 kbit/s. It also says RS485 transmission is possible on this cable with the bit rate limited to 1.5 Mbit/s. Characteristic impedance is 100 ± 20 Ohm. Loop resistance is max. 44 ohm/km. Peak operating voltage is 250 V, and the page says that voltage is not for power applications. Fixed-installation temperature is -30°C to +80°C. Temperature during installation is -5°C to +50°C. Minimum bend radius for fixed installation is 10 times the outer diameter. Test voltage core to core is 1500 V rms.
Article 2170234 is UNITRONIC BUS PA (BU), 1 x 2 x 1.3, outer diameter 8 mm. Article 2170235 is the black version, UNITRONIC BUS PA (BK), with the same 1 x 2 x 1.3 and the same 8 mm outer diameter. The Fast Connect articles are 2170334, blue, and 2170335, black, both 1 x 2 x 1 and both 8 mm outer diameter. The makeup lines describe a blue sheath, RAL 5015, for an intrinsically safe area, and a black sheath, RAL 9005. Conventional makeup lists a stranded conductor and copper braiding. Fast Connect makeup lists bare copper wire, a Fast Connect inner sheath, and a copper braid. PI's PA reference cable in Table 1-4 is a shielded twisted pair, nominal core 0.8 mm² (AWG 18), loop resistance 44 ohm/km, and impedance 100 Ω ± 20% at 31.25 kHz. LAPP's loop-resistance maximum and impedance cell match those two PI figures. LAPP's conductor column is a diameter in millimeters, 1.3 or 1, and the page does not print 0.8 mm², so this page does not rename 1.3 mm as AWG 18.
| Item | Belden 3079A | LAPP UNITRONIC BUS PA | PI interconnection guideline, Version 1.4 |
|---|---|---|---|
| Impedance | 150 Ohm | 100 ± 20 Ohm | DP Type A: 135 to 165 ohm at 3 to 20 MHz. PA: 100 Ω ± 20% at 31.25 kHz. |
| Conductors | 1 pair, 22 AWG solid | 1 x 2 x 1.3 mm on 2170234, or 1 x 2 x 1 mm on 2170334 | DP solid core AWG 22/1. PA nominal core 0.8 mm² (AWG 18). |
| Jacket on the opened page | Violet or chrome put-ups, PVC, 0.315 in (8.00 mm) | Blue RAL 5015 or black RAL 9005, outer diameter 8 mm | Jacket color is not in Table 1-3 or Table 1-4. |
| Temperature | -30°C to +75°C operating | -30°C to +80°C fixed installation | Not in the two cable tables cited here. |
DP M12 is B-coded, and the PA figure is A-coded
For PROFIBUS RS-485 in IP 65 or higher, section 4.1.2 says the connectors comply with IEC 61076-2-101, variant 5-pole B-coding. The female connector on the device side assigns pin 1 to power supply plus (P5V), pin 2 to RxD/TxD-N, the A-line (green), pin 3 to data ground, pin 4 to RxD/TxD-P, the B-line (red), and pin 5 to not connected. The shield is the thread. The male connector on the device side leaves pins 1, 3, and 5 not connected, and keeps pin 2 on the A-line (green) and pin 4 on the B-line (red). The guideline says existing devices with pin 5 connected still conform, and that new devices shall not use pin 5. Belden's insulation color code is red and green, which are the colors named in those A-line and B-line cells. The Belden page does not print this pin table.
The M12 pin table in section 4.4 is for IEC 61158-2, and the figure caption says IEC 61076-2-101 A coding. Contact 1 is Data + with the option of power +, contact 2 is not connected, contact 3 is Data - with the option of power -, contact 4 is not connected, and the thread is the shield. The text says existing Type 3 devices with pin 4 connected still conform, and that new devices shall not use pin 4. That A-coded four-position assignment is the PA connector section. It is not the 5-pole B-coded DP assignment above. A PROFINET M12 is a third key, covered on the D-coded and X-coded page.
Which cable matches the network on the drawing
A DP drawing that asks for Type A impedance uses 3079A's 150 Ohm and 22 AWG solid pair, and a 5-pole B-coded M12 when the connector is the one in section 4.1.2. A PA drawing that asks for IEC 61158-2 uses a UNITRONIC BUS PA article at 100 ± 20 Ohm and 31.25 kbit/s, blue or black as the area requires, and the A-coded pin table when that section is the connector. Belden's suitable-application sentence names Profibus DP or PA for 3079A. The impedance cell on that page remains 150 Ohm. A device maker can accept 3079A on a PA port. The electrical match to the PA reference cable and to articles 2170234 and 2170334 is the 100 ± 20 Ohm cell, not the 150 Ohm cell.
The PA page's RS485 sentence, limited to 1.5 Mbit/s, does not move the impedance cell into the DP window of 135 to 165 ohm. The DP guideline says that when the baud rate is higher than 1.5 Mbit/s, branches shall be avoided. That branch rule is about the tee, not a reason to swap the two cables.
What to copy onto the cable line
- Network: PROFIBUS DP or PROFIBUS PA.
- Part: 3079A, including the violet or chrome put-up, or UNITRONIC BUS PA 2170234, 2170235, 2170334, or 2170335.
- Impedance cell: 150 Ohm, or 100 ± 20 Ohm.
- Bit rate when the cable is PA: 31.25 kbit/s, or the 1.5 Mbit/s RS485 limit if that sentence is the one in use.
- M12: 5-pole B-coding for the DP section, or A-coding for the IEC 61158-2 section.
- Jacket color and outer diameter from the row.
Questions these pages answer
Does a violet jacket make 3079A a PA cable?
Violet is one jacket put-up of 3079A, next to chrome. The impedance cell is 150 Ohm on the product page. The PA articles opened today are blue or black and print 100 ± 20 Ohm.
Are 8.00 mm and 8 mm the same cable?
Belden prints 0.315 in (8.00 mm) for 3079A. LAPP prints 8 mm for the UNITRONIC BUS PA articles. The diameters are close. The impedance, the pair construction, and the jacket colors are the fields that separate them.
Can DP pin 5 be used on a new device?
The guideline says new devices shall not use pin 5, and that existing devices with pin 5 connected still conform. New cables follow the not-connected cell for pin 5 on the male and female tables in section 4.1.2.
Sources
3079A impedance, gauge, diameter, colors, temperature, voltage, bend, and put-ups are from the Belden page. UNITRONIC BUS PA articles, impedance, loop resistance, bit rate, temperature, bend, and sheath colors are from the LAPP page. DP Type A and PA reference parameters, and the B-coded and A-coded M12 assignments, are from PROFIBUS Interconnection Technology Version 1.4. All three were opened October 23, 2026.