Liquid cooling
CEJN UQD at 10 bar or Danfoss by Size
Use CEJN when the family cell of 10 bar is the pressure. Use the Danfoss row when the size has its own bar rating, from 20 bar on UQD02 to 6.9 bar on UQD06.
On this page
Use the CEJN UQD family when the pressure on the request is the one cell that page prints for every listed diameter: 10 bar, as of October 25, 2026, beside nominal flow diameters of 3.2, 6.4, 9.5, and 12.7 mm, in stainless steel AISI 303 with double EPDM seals. Use a Danfoss Hansen size row when the pressure is the cell for that size. As of the same day, the fact sheet lists 20 bar (290 psi) on UQD02 for the connected coupling, the socket, and the plug; 16 bar (232 psi) on UQD04 for all three; 6.9 bar (100 psi) on UQD06 for all three; and 8.9 bar (129 psi) connected on UQD08, with 6.9 bar (100 psi) on the UQD08 socket and on the UQD08 plug. CEJN's page, reopened October 26, 2026, says any manufacturer's products are connectable when they follow the UQD specification. The Danfoss file opened the same day says the coupling is designed per the OCP UQD specification and that it complies with OCP. Neither page names a coolant. OCP, Gates, and CPC windows are on the coupling ratings page.
One family cell, or a bar rating on each size
CEJN's technical-data table, opened October 25, 2026, has three rows: nominal flow diameter 3.2, 6.4, 9.5, and 12.7 mm; max working pressure 10 bar; main material stainless steel AISI 303. The page names four sizes, UQD02, UQD04, UQD06, and UQD08, in a separate sentence from the diameter cell and from the 10 bar cell. A request that uses this page copies 10 bar for the family. A size-to-diameter pair comes from a table that prints the pair.
The Danfoss feature list, on the fact sheet opened October 25, 2026, says typical working pressure is 6.9 bar, up to 20 bar for smaller sizes. The size table is the place those words become a cell. UQD02 body size is 1/8 in, nominal flow diameter 3.16 mm, maximum operating pressure 20 bar (290 psi) connected, on the socket, and on the plug, minimum burst 60 bar (870 psi), rated flow 2.1 lpm (0.6 gpm). UQD04 body size is 1/4 in, flow diameter 6.3 mm, 16 bar (232 psi) on all three pressure columns, burst 48 bar (696 psi), rated flow 6.4 lpm (1.7 gpm). UQD06 body size is 3/8 in, flow diameter 7.9 mm, 6.9 bar (100 psi) on all three, burst 20.7 bar (300 psi), rated flow 11.4 lpm (3.0 gpm). UQD08 body size is 1/2 in, flow diameter 10 mm, 8.9 bar (129 psi) connected, 6.9 bar (100 psi) on the socket and on the plug, burst 20.7 bar (300 psi), rated flow 17.8 lpm (4.7 gpm). The rated-flow footnote says that flow is the reference used to measure pressure drop and to determine the published Cv. This page does not quote a Cv number from that table.
| Item | CEJN UQD page | Danfoss Hansen fact sheet |
|---|---|---|
| How pressure is printed | One cell, 10 bar, for the family | A bar cell on each size row |
| UQD02 | Size named. No separate bar cell. | 20 bar (290 psi) connected, socket, and plug |
| UQD04 | Size named. No separate bar cell. | 16 bar (232 psi) connected, socket, and plug |
| UQD06 | Size named. No separate bar cell. | 6.9 bar (100 psi) connected, socket, and plug |
| UQD08 | Size named. No separate bar cell. | 8.9 bar (129 psi) connected. 6.9 bar (100 psi) socket and plug. |
| Body | AISI 303 | 303/304 stainless on the feature list |
| Seal | Double EPDM | EPDM-P, peroxide cured |
| Coolant name | Not printed | Not printed |
Stainless and EPDM on both pages, with different temperature lines
CEJN's features, as of October 25, 2026, name redundant sealing with double EPDM rubber seals, a stainless steel design, and a spill-free connection with minimum air intrusion. The hose connection is a push-lock hose barb. The page says the barb locks the hose without ferrules or hose clamps, and that a plastic stop ring marks a fitted hose. Hot-swappable on that page means connection and disconnection under pressure. The technical-data table has no temperature row. A temperature on a CEJN line has to come from a page that prints one.
The Danfoss feature list says the operating temperature range is 5°C (41°F) to 65°C (149°F). Standard seal material is EPDM-P, peroxide cured. Standard material is 303/304 stainless steel. The sheet says those peroxide-cured seals and O-rings are certified to IEC 62368-1 G.15.2.3 under file MH67791, Volume 1, as read October 25, 2026. The seal table lists EPDM-P from -40°C to +150°C (-40°F to +302°F). That elastomer range is wider than the 5°C to 65°C operating line. Quote the line that matches the question: the coupling operating band, or the elastomer band. The size-by-size pressures and the OCP flow column are also on the UQD size page.
The millimeter lists are not one table
CEJN prints 3.2, 6.4, 9.5, and 12.7 mm in a single flow-diameter cell. Danfoss prints 3.16 mm on UQD02, 6.3 mm on UQD04, 7.9 mm on UQD06, and 10 mm on UQD08. A request copies the millimeters from the page it is using. It does not assign 3.2 mm to UQD02 because CEJN did not print that pair, and it does not replace Danfoss 10 mm with CEJN 12.7 mm.
CEJN's page says any manufacturer's products are connectable when they follow the UQD specification. That sentence is why a CEJN body and a Danfoss body can sit on one comparison. It does not assign CEJN's 10 bar to a Danfoss part number. Staubli CGD and SPT/CG are a different pair of series, with their own pressures, on the CGD and SPT/CG page. Supplier context for other UQD makers is on the quick-disconnect page.
Danfoss prints a connect force and a torque for each size
The Danfoss performance table, as of October 25, 2026, lists force to connect of 48 N (10.79 lb) on UQD02, 50 N (11.24 lb) on UQD04, 73 N (16.41 lb) on UQD06, and 87 N (19.56 lb) on UQD08. Recommended torque on the same rows is ORB 7/16-20 at 9 to 10 N·m and BSP 1/8 inch at 8 to 9 N·m for UQD02; ORB 9/16-18 at 15 to 17 N·m and BSP 3/8 inch at 18 to 20 N·m for UQD04; ORB 3/4-16 at 25 to 28 N·m and BSP 3/8 inch at 18 to 20 N·m for UQD06; ORB 7/8-14 at 30 to 33 N·m and BSP 1/2 inch at 34 to 37 N·m for UQD08. CEJN's technical-data table has no force row and no torque row. A compressed-air force table on the Danfoss sheet leaves the UQD02 cell at 100 psi empty, so the figures above are the force-to-connect row.
Both pages talk about fluid compatibility and name no coolant
CEJN's feature line says a stainless steel design is for improved fluid compatibility. The Danfoss feature line says 303/304 stainless steel provides broad fluid compatibility. Neither sentence names glycol, dielectric coolant, deionized water, or PAO. The coolant field on the request stays open until a fluid specification names it. Pressure, body, and seal can still be copied from the page in front of you.
What to copy onto the coupling line
- Maker and size: CEJN family, or Danfoss UQD02, UQD04, UQD06, or UQD08, from the page opened October 25, 2026.
- Pressure: 10 bar on the CEJN cell, or the Danfoss bar cell for that size, including 8.9 bar connected and 6.9 bar on the UQD08 socket and plug.
- Body and seal: AISI 303 and double EPDM, or 303/304 and EPDM-P.
- Flow diameter from the page you are using. CEJN's 3.2, 6.4, 9.5, and 12.7 mm stay in one cell.
- Temperature: blank on the CEJN technical-data table. On Danfoss, 5°C to 65°C for the coupling, or -40°C to +150°C for the EPDM-P seal table.
- Coolant: the name from the fluid specification. These two pages do not print one.
Questions these two pages answer
Does 10 bar apply to one CEJN size only?
The CEJN technical-data table prints 10 bar once, as of October 25, 2026, next to the four diameters in one cell. There is no second pressure row. Danfoss is the page that changes the bar rating by size.
Why does UQD08 have two Danfoss pressures?
On the sheet opened October 25, 2026, UQD08 connected is 8.9 bar (129 psi). The socket column and the plug column are each 6.9 bar (100 psi). UQD02, UQD04, and UQD06 print the same bar figure in all three columns. The request names which column it is using.
Which Danfoss temperature is the operating limit?
The feature list states 5°C (41°F) to 65°C (149°F) as the operating temperature range. The elastomer table states -40°C to +150°C for EPDM-P. CEJN's technical-data table prints neither line. A CEJN temperature stays blank until a CEJN page prints one.
Sources
The 10 bar cell, the four diameters, AISI 303, double EPDM, the push-lock barb, and the connectable-products sentence are from the CEJN UQD page, reopened October 26, 2026. Size pressures, flow, body, seal, the 5°C to 65°C line, the EPDM-P range, file MH67791, force, and torque are from the Danfoss file opened October 26, 2026. That file prints September 2026 and footer AI423953312825en-000106. The URL path still contains AI423953312825en-001401. The pressure cells match the cells recorded on October 25, 2026. The file says designed per the OCP UQD specification and complies with OCP. Cv, air inclusion, and fluid loss were left off because the size-table columns do not line up with those headers. Neither page names a coolant. A Parker stainless UQD row with one pressure for sizes 02 through 08 is on the Parker and Danfoss page.