Liquid cooling
Parker UQD at 150 psi or Danfoss by Size
Use Parker when one 150 psi (10.3 bar) cell covers sizes 02 through 08 at 0°C to 70°C. Use Danfoss when the size has its own bar rating, from 20 bar on UQD02 to 6.9 bar on UQD06.
On this page
Use the Parker hand-mate UQD row when the working pressure is one cell for sizes 02, 04, 06, and 08. The brochure opened October 26, 2026 prints 150 psi (10.3 bar), a rated working temperature of 0°C to 70°C, a stainless steel socket, a stainless steel plug, and EPDM seals. Use a Danfoss Hansen size row when the pressure is the cell for that size. The fact sheet opened the same day lists 20 bar (290 psi) on UQD02 for the connected coupling, the socket, and the plug; 16 bar (232 psi) on UQD04 for all three; 6.9 bar (100 psi) on UQD06 for all three; and 8.9 bar (129 psi) connected on UQD08, with 6.9 bar (100 psi) on the UQD08 socket and on the UQD08 plug. Danfoss lists an operating temperature of 5°C (41°F) to 65°C (149°F). CEJN's UQD page, opened the same day, says any manufacturer's products are connectable when they follow the UQD specification. Parker says its UQD is based on an OCP design. Danfoss says its coupling is designed per the OCP UQD specification. CEJN's own 10 bar cell is on the CEJN and Danfoss page.
One brochure cell, or a bar rating on each Danfoss size
The Parker selection guide, in the September 2026 brochure opened October 26, 2026, lists body sizes 02, 04, 06, and 08, hand-mate, stainless steel, EPDM, working temperature 0°C to 70°C, storage temperature -40°C to 120°C, and working pressure 150 psi / 10.3 bar, under the series name UQD. The UQD specification table on the same brochure repeats a maximum working pressure of 150 psi / 10.3 bar. A request that uses this brochure copies 150 psi (10.3 bar) for each of those four sizes, including UQD08.
The Danfoss feature list, on the file opened October 26, 2026, says typical working pressure is 6.9 bar, up to 20 bar for smaller sizes. The size table is the place those words become a cell. UQD02 body size is 1/8 in, nominal flow diameter 3.16 mm, 20 bar (290 psi) connected, on the socket, and on the plug, minimum burst 60 bar (870 psi), rated flow 2.1 lpm (0.6 gpm). UQD04 body size is 1/4 in, flow diameter 6.3 mm, 16 bar (232 psi) on all three pressure columns, burst 48 bar (696 psi), rated flow 6.4 lpm (1.7 gpm). UQD06 body size is 3/8 in, flow diameter 7.9 mm, 6.9 bar (100 psi) on all three, burst 20.7 bar (300 psi), rated flow 11.4 lpm (3.0 gpm). UQD08 body size is 1/2 in, flow diameter 10 mm, 8.9 bar (129 psi) connected, 6.9 bar (100 psi) on the socket and on the plug, burst 20.7 bar (300 psi), rated flow 17.8 lpm (4.7 gpm). The rated-flow footnote says that flow is the reference used to measure pressure drop and to determine the published Cv. This page does not quote a Cv number from the Danfoss table.
| Item | Parker hand-mate UQD | Danfoss Hansen UQD |
|---|---|---|
| How pressure is printed | One cell, 150 psi (10.3 bar), for sizes 02, 04, 06, and 08 | A bar cell on each size row |
| UQD02 | 150 psi (10.3 bar) | 20 bar (290 psi) connected, socket, and plug |
| UQD04 | 150 psi (10.3 bar) | 16 bar (232 psi) connected, socket, and plug |
| UQD06 | 150 psi (10.3 bar) | 6.9 bar (100 psi) connected, socket, and plug |
| UQD08 | 150 psi (10.3 bar) | 8.9 bar (129 psi) connected. 6.9 bar (100 psi) socket and plug. |
| Working temperature | 0°C to 70°C | 5°C (41°F) to 65°C (149°F) |
| Body and seal | Stainless steel socket and plug, EPDM | 303/304 stainless steel, EPDM-P |
| Mate | Hand-mate on the selection-guide row | Push-to-connect on the feature list |
0°C to 70°C on Parker, 5°C to 65°C on Danfoss
Parker's UQD specification table, as of October 26, 2026, lists rated working temperature 0°C to 70°C. The same cell says an extended temperature range is possible and tells the reader to contact Parker. Storage and shipping temperature on that table is -40°C to 120°C. The selection-guide row prints the same working band and the same storage band. The brochure cover date is September 2026.
Danfoss lists the operating temperature range as 5°C (41°F) to 65°C (149°F). Standard seal material is EPDM-P, peroxide cured. Standard material is 303/304 stainless steel. The seal table lists EPDM-P from -40°C to +150°C (-40°F to +302°F). That elastomer range is wider than the operating line. Quote the line that matches the question: the coupling operating band, or the elastomer band. The file also says the peroxide-cured seals and O-rings are certified to IEC 62368-1 G.15.2.3 under file MH67791, Volume 1. The footer on the file is AI423953312825en-000106, September 2026. The URL path still contains AI423953312825en-001401.
Parker prints a direction on each Cv. Danfoss Cv stays off this page
The Parker table headed CV Values - UQD v1, as of October 26, 2026, prints two coefficients for each size. UQD02 is 0.33 plug to socket and 0.30 socket to plug. UQD04 is 1.22 plug to socket and 1.10 socket to plug. UQD06 is 2.60 plug to socket and 2.25 socket to plug. UQD08 is 3.90 plug to socket and 4.09 socket to plug. A request that copies a Parker Cv names the direction. The label on the table is UQD v1.
The Danfoss size table prints rated flow, then more figures whose headers in the file sit too close together to assign a Cv, an air-inclusion volume, or a fluid-loss volume. Those three stay off this page. Rated flow is the cell quoted above. OCP maximum Cv values, and the Gates minimum Cv that sits above one of them, are on the UQD size page.
Pounds at a stated psi, or newtons on a force-to-connect row
Parker's connect-force row is labeled Connect Force - UQD v1, as of October 26, 2026. UQD02 is 14 lbs at 0 psi, 15 lbs at 14 psi, and 20 lbs at 100 psi. UQD04 is 20 lbs at 0 psi, 22 lbs at 14 psi, and 35 lbs at 100 psi. UQD06 is 18 lbs at 0 psi, 22 lbs at 14 psi, and 45 lbs at 100 psi. UQD08 is 26 lbs at 0 psi, 33 lbs at 14 psi, and 63 lbs at 100 psi. The request names the pressure column.
Danfoss lists force to connect of 48 N (10.79 lb) on UQD02, 50 N (11.24 lb) on UQD04, 73 N (16.41 lb) on UQD06, and 87 N (19.56 lb) on UQD08, as of October 26, 2026. That row leaves the psi columns off the newton figure. The two force tables use different labels. Copy the table whose unit the request is using. Recommended torque on the Danfoss rows is ORB 7/16-20 at 9 to 10 N·m and BSP 1/8 inch at 8 to 9 N·m for UQD02; ORB 9/16-18 at 15 to 17 N·m and BSP 3/8 inch at 18 to 20 N·m for UQD04; ORB 3/4-16 at 25 to 28 N·m and BSP 3/8 inch at 18 to 20 N·m for UQD06; ORB 7/8-14 at 30 to 33 N·m and BSP 1/2 inch at 34 to 37 N·m for UQD08.
Hand-mate UQD is the Parker row in this comparison
The Parker selection guide also lists UQDB at sizes 02, 04, 06, and 08, blind-mate, stainless steel, EPDM, 0°C to 70°C, storage -40°C to 120°C, and the same 150 psi / 10.3 bar, as of October 26, 2026. That row is the blind-mate series. This comparison uses the hand-mate UQD row. Danfoss describes the UQD coupling as push-to-connect. The brochure says the UQD series is based on an OCP design and approved on the Nvidia Partner Network, which that sentence abbreviates as NPN. A feature line says the couplings are interchangeable with other UQD-approved manufacturers. CEJN's connectable-products sentence is the second page that puts two UQD makers on one job. Staubli CGD and SPT/CG are a different pair of series, on the CGD and SPT/CG page.
Danfoss also prints color-anodized aluminum sleeves and red and blue coding on the socket sleeve and on the plug O-ring, as of October 26, 2026. The Parker material cell for this UQD table names stainless steel and EPDM. A sleeve alloy on a Parker line has to come from a cell that prints one. The brochure's flow diagrams for UQD v1 are labeled Water. This page does not read a flow number off those diagrams. Danfoss rated flow is the liter-per-minute cell in the size table.
What to copy onto the coupling line
- Maker and size: Parker hand-mate UQD, sizes 02, 04, 06, or 08, or Danfoss UQD02, UQD04, UQD06, or UQD08, from the file opened October 26, 2026.
- Pressure: 150 psi (10.3 bar) on the Parker cell, or the Danfoss bar cell for that size, including 8.9 bar connected and 6.9 bar on the UQD08 socket and plug.
- Temperature: 0°C to 70°C on Parker, or 5°C to 65°C on the Danfoss operating line. The Danfoss EPDM-P seal table is -40°C to +150°C.
- Body and seal: stainless steel and EPDM, or 303/304 and EPDM-P.
- Cv, on Parker only, with the direction: plug to socket, or socket to plug, from the UQD v1 table.
- Force: the Parker pound figure at 0 psi, 14 psi, or 100 psi, or the Danfoss newton figure. Keep the tables separate.
Questions these two files answer
Does 150 psi apply to every Parker size on this row?
The selection-guide row and the specification table each print 150 psi / 10.3 bar once for the hand-mate UQD series, as of October 26, 2026. Sizes 02, 04, 06, and 08 share that cell. Danfoss is the file that changes the bar rating by size.
Which temperature is the working limit?
Parker prints 0°C to 70°C as the rated working temperature, as of October 26, 2026, and says an extended range is a question for Parker. Danfoss prints 5°C (41°F) to 65°C (149°F) as the operating range, and -40°C to +150°C on the EPDM-P seal table. The request names the line it is using.
Can a Parker Cv be copied onto a Danfoss size?
Parker prints the direction on each UQD v1 coefficient. UQD08, for example, is 3.90 plug to socket and 4.09 socket to plug, as of October 26, 2026. The Danfoss Cv column was left unread because the headers do not separate cleanly from the neighboring volume columns. A Danfoss Cv stays off the request until a Danfoss cell can be quoted on its own.
Sources
The 150 psi (10.3 bar) cell, the 0°C to 70°C line, the stainless and EPDM materials, the UQD v1 Cv directions, and the connect-force pounds are from the Parker thermal management brochure, cover date September 2026. Danfoss pressures, rated flow, the 5°C to 65°C line, the EPDM-P range, file MH67791, and force to connect are from the fact sheet whose footer is AI423953312825en-000106. The connectable-products sentence is from the CEJN UQD page. All three were opened October 26, 2026. The brochure cell that pairs two milliliter figures for spillage and air inclusion does not say which figure is which, so those pairs are omitted. Danfoss Cv, air inclusion, and fluid loss are omitted for the same column reason already recorded on the CEJN comparison. Socket part numbers in the Parker dimension tables were not copied.